InteliPro, SW version 1.4, ©ComAp April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-40
Library of alarm messages
ActCallCH1Fail
error during sending an SMS to a number stated in the setpoint SMS/E-mail ->
TelNo/Addr Ch1
ActCallCH2Fail
error during sending an SMS to a number stated in the setpoint SMS/E-mail ->
TelNo/Addr Ch2
Low BackupBatt
Backup battery is low
Wrn Aux Volt
over or undervoltage of the power supply
M L1 neg
phase sequence is correct, L1 is in antiphase
M L2 neg
phase sequence is correct, L2 is in antiphase
M L3 neg
phase sequence is correct, L3 is in antiphase
M ph opposed
opposed phase sequence
M ph+L1 neg
phase sequence is opposite, L1 is in antiphase
M ph+L2 neg
phase sequence is opposite, L2 is in antiphase
M ph+L3 neg
phase sequence is opposite, L3 is in antiphase
Trp Vm1>
trip due to exceeding of the first stage overvoltage in phase 1
Trp Vm1>>
trip due to exceeding of the second stage overvoltage in phase 1
Trp Vm1<
trip due to exceeding of the first stage undervoltage in phase 1
Trp Vm1<<
trip due to exceeding of the first stage undervoltage in phase 1
Trp Vm2>
trip due to exceeding of the first stage overvoltage in phase 2
Trp Vm2>>
trip due to exceeding of the second stage overvoltage in phase 2
Trp Vm2<
trip due to exceeding of the first stage undervoltage in phase 2
Trp Vm2<<
trip due to exceeding of the first stage undervoltage in phase 2
Trp Vm3>
trip due to exceeding of the first stage overvoltage in phase 3
Trp Vm3>>
trip due to exceeding of the second stage overvoltage in phase 3
Trp Vm3<
trip due to exceeding of the first stage undervoltage in phase 3
Trp Vm3<<
trip due to exceeding of the first stage undervoltage in phase 3
Trp Vm12>
trip due to exceeding of the first stage overvoltage between phases 1 and 2
Trp Vm12>>
trip due to exceeding of the second stage overvoltage between phases 1 and 2
Trp Vm12<
trip due to exceeding of the first stage undervoltage between phases 1 and 2
Trp Vm12<<
trip due to exceeding of the first stage undervoltage between phases 1 and 2
Trp Vm23>
trip due to exceeding of the first stage overvoltage between phases 2 and 3
Trp Vm23>>
trip due to exceeding of the second stage overvoltage between phases 2 and 3
Trp Vm23<
trip due to exceeding of the first stage undervoltage between phases 2 and 3
Trp Vm23<<
trip due to exceeding of the first stage undervoltage between phases 2 and 3
Trp Vm31>
trip due to exceeding of the first stage overvoltage between phases 3 and 1
Trp Vm31>>
trip due to exceeding of the second stage overvoltage between phases 3 and 1
Trp Vm31<
trip due to exceeding of the first stage undervoltage between phases 3 and 1
Trp Vm31<<
trip due to exceeding of the first stage undervoltage between phases 3 and 1
Trp V Unb
trip due to voltage unbalance
Trp V Neg Seq
trip due to exceeding of overvoltage limit of negative sequence
Trp V Pos Seq
trip due to exceeding of undervoltage limit of positive sequence
Trp fm>
trip due to exceeding of the first stage overfrequency

Table of Contents

Other manuals for ComAp InteliPro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliPro and is the answer not in the manual?

ComAp InteliPro Specifications

General IconGeneral
BrandComAp
ModelInteliPro
CategoryRelays
LanguageEnglish

Related product manuals