InteliPro, SW version 1.4, ©ComAp April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
1-13
NOTE:
The fail sensor alarm is issued if the measured resistance is smaller than one half of the first (lowest)
point of the sensor curve characteristic or is greater than 112,5% of the last (greatest) point of the
sensor curve characteristic.
WIRING OF ANALOG INPUTS - GROUNDED SENSORS
WIRING OF ANALOG INPUTS - ISOLATED SENSORS
Tristate inputs
Analog inputs can be used also as binary or tristate, i.e. for contact sensors without or with circuit
check.Thethresholdlevelis750Ω.Incaseoftristate,valueslowerthan10Ωand valuesover2400Ω
are evaluated as sensor failure (short or open circuit).