3.8.4 6-3* Analog Input 3 General Purpose
I/O MCB 101
Parameter group for conguring the scale and limits for
analog input 3 (X30/11) in VLT
®
General Purpose I/O MCB
101.
6-30 Terminal X30/11 Low Voltage
Range: Function:
0.07 V* [ 0 - par. 6-31
V]
Sets the analog input scaling value
to correspond to the low reference
feedback value (set in
parameter 6-34 Term. X30/11 Low
Ref./Feedb. Value).
6-31 Terminal X30/11 High Voltage
Range: Function:
10 V* [ par. 6-30 -
10 V]
Sets the analog input scaling value
to correspond to the high reference
feedback value (set in
parameter 6-35 Term. X30/11 High
Ref./Feedb. Value).
6-34 Term. X30/11 Low Ref./Feedb. Value
Range: Function:
0* [-999999.999
- 999999.999 ]
Sets the analog input scaling value
to correspond to the low voltage
value (set in
parameter 6-30 Terminal X30/11 Low
Voltage).
6-35 Term. X30/11 High Ref./Feedb. Value
Range: Function:
100* [-999999.999
- 999999.999 ]
Sets the analog input scaling value
to correspond to the high-voltage
value (set in
parameter 6-31 Terminal X30/11 High
Voltage).
6-36 Term. X30/11 Filter Time Constant
Range: Function:
0.005 s* [0.005 - 10 s]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the lter time constant. This
constant is a rst-order digital low-
pass lter time for suppressing
electrical noise in terminal X30/11.
A high value improves dampening
but also increases the delay
through the lter.
6-37 Term. X30/11 Live Zero
Option: Function:
This parameter makes it possible to
disable the live zero-monitoring. For
example, to be used if the analog
outputs are used in a decentral I/O
system (when an analog output
does not full any control function,
but feeds a data storage device).
[0] Disabled
[1] * Enabled
3.8.5 6-4* Analog Input X30/12
Parameter group for conguring the scale and limits for
analog input 4 (X30/12) in VLT
®
General Purpose I/O MCB
101.
6-40 Terminal X30/12 Low Voltage
Range: Function:
0.07 V* [ 0 - par. 6-41
V]
Sets the analog input scaling value
to correspond to the low reference
feedback value set in
parameter 6-44 Term. X30/12 Low
Ref./Feedb. Value.
6-41 Terminal X30/12 High Voltage
Range: Function:
10 V* [ par. 6-40 -
10 V]
Sets the analog input scaling value
to correspond to the high reference
feedback value set in
parameter 6-45 Term. X30/12 High
Ref./Feedb. Value.
6-44 Term. X30/12 Low Ref./Feedb. Value
Range: Function:
0* [-999999.999
- 999999.999 ]
Sets the analog output scaling
value to correspond to the low
voltage value set in
parameter 6-40 Terminal X30/12 Low
Voltage.
6-45 Term. X30/12 High Ref./Feedb. Value
Range: Function:
100* [-999999.999
- 999999.999 ]
Sets the analog input scaling value
to correspond to the high voltage
value set in parameter 6-41 Terminal
X30/12 High Voltage.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 109
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals