22-50 End of Curve Function
Option: Function:
NOTICE
Automatic restart resets the
alarm and restarts the system.
NOTICE
Do not set
parameter 14-20 Reset Mode, to
[13] Innite auto reset, when
parameter 22-50 End of Curve
Function is set to [2] Alarm.
Doing so causes the frequency
converter to continuously cycle
between running and stopping
when an end-of-curve
condition is detected.
NOTICE
If the frequency converter is
equipped with a constant
speed bypass with an
automatic bypass function that
starts the bypass if the
frequency converter
experiences a persistent alarm
condition, be sure to disable
the automatic bypass function,
if [2] Alarm or [3] Man. Reset
Alarm is selected as the end-
of-curve function.
[0] * O End-of-curve monitoring is not
active.
[1] Warning The frequency converter continues
to run, but activates an end-of-
curve warning (warning 94, End of
curve). A frequency converter digital
output or a serial communication
bus can communicate a warning to
other equipment.
[2] Alarm The frequency converter stops
running and activates an end-of-
curve alarm (alarm 94, End of curve).
A frequency converter digital
output or a serial communication
bus can communicate an alarm to
other equipment.
[3] Man. Reset
Alarm
The frequency converter stops
running and activates an end-of-
curve alarm (alarm 94, End of curve).
A frequency converter digital
output or a eldbus can
22-50 End of Curve Function
Option: Function:
communicate an alarm to other
equipment.
[4] Stop and Trip
22-51 End of Curve Delay
Range: Function:
10 s* [0 - 600 s] When an end-of-curve condition is
detected, a timer is activated. When
the time set in this parameter
expires, and the end-of-curve
condition is steady during the
entire period, the function set in
parameter 22-50 End of Curve
Function is activated. If the
condition disappears before the
timer expires, the timer is reset.
3.20.5 22-6* Broken Belt Detection
The broken-belt detection can be used in both closed-loop
and open-loop systems for pumps, fans, and compressors.
If the estimated motor torque is below the broken-belt
torque value (parameter 22-61 Broken Belt Torque), and the
frequency converter output frequency is above or equal to
15 Hz, the broken-belt function (parameter 22-60 Broken
Belt Function) is performed.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 207
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals