3.15 Parameters: 15-** Main Menu - Drive
Information
Parameter group containing frequency converter
information such as operating data, hardware congu-
ration, and software versions.
3.15.1 15-0* Operating Data
15-00 Operating hours
Range: Function:
0 h* [0 -
2147483647 h]
View how many hours the
frequency converter has run. The
value is saved when the frequency
converter is turned o.
15-01 Running Hours
Range: Function:
0 h* [0 -
2147483647 h]
View how many hours the motor
has run. Reset the counter in
parameter 15-07 Reset Running
Hours Counter. The value is saved
when the frequency converter is
turned o.
15-02 kWh Counter
Range: Function:
0 kWh* [0 -
2147483647
kWh]
Register the power consumption of
the motor as an average value over
1 hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0* [0 -
2147483647 ]
View the number of times the
frequency converter has been
powered up.
15-04 Over Temp's
Range: Function:
0* [0 - 65535 ] View the number of frequency
converter temperature faults.
15-05 Over Volt's
Range: Function:
0* [0 - 65535 ] View the number of frequency
converter overvoltages.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset No reset of the kWh counter is
required.
15-06 Reset kWh Counter
Option: Function:
[1] Reset counter Press [OK] to reset the kWh counter
to 0 (see parameter 15-02 kWh
Counter).
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset No reset of the running hours
counter is required.
[1] Reset counter Select [1] Reset counter and press
[OK] to reset the running hours
counter (parameter 15-01 Running
Hours) and parameter 15-08 Number
of Starts to 0 (see also
parameter 15-01 Running Hours).
15-08 Number of Starts
Range: Function:
0* [0 -
2147483647 ]
NOTICE
This parameter is reset when
resetting parameter 15-07 Reset
Running Hours Counter.
This is a readout parameter only.
The counter shows the number of
starts and stops caused by a normal
start/stop command and/or when
entering/leaving sleep mode.
3.15.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (parameter 15-10 Logging Source) at individual rates
(parameter 15-11 Logging Interval). A trigger event
(parameter 15-12 Trigger Event) and window
(parameter 15-14 Samples Before Trigger) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to be
logged.
[0] * None
[15] Readout:
actual setup
[1397] Alert Alarm
Word
[1398] Alert Warning
Word
[1399] Alert Status
Word
[1600] Control Word
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 157
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals