3.15 Parameters: 15-** Main Menu - Drive
Information
Parameter group containing frequency converter
information such as operating data, hardware congu-
ration, and software versions.
3.15.1 15-0* Operating Data
15-00 Operating hours
Range: Function:
0 h* [0 -
2147483647 h]
View how many hours the
frequency converter has run. The
value is saved when the frequency
converter is turned o.
15-01 Running Hours
Range: Function:
0 h* [0 -
2147483647 h]
View how many hours the motor
has run. Reset the counter in
parameter 15-07 Reset Running
Hours Counter. The value is saved
when the frequency converter is
turned o.
15-02 kWh Counter
Range: Function:
0 kWh* [0 -
2147483647
kWh]
Register the power consumption of
the motor as an average value over
1 hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0* [0 -
2147483647 ]
View the number of times the
frequency converter has been
powered up.
15-04 Over Temp's
Range: Function:
0* [0 - 65535 ] View the number of frequency
converter temperature faults.
15-05 Over Volt's
Range: Function:
0* [0 - 65535 ] View the number of frequency
converter overvoltages.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset No reset of the kWh counter is
required.
15-06 Reset kWh Counter
Option: Function:
[1] Reset counter Press [OK] to reset the kWh counter
to 0 (see parameter 15-02 kWh
Counter).
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset No reset of the running hours
counter is required.
[1] Reset counter Select [1] Reset counter and press
[OK] to reset the running hours
counter (parameter 15-01 Running
Hours) and parameter 15-08 Number
of Starts to 0 (see also
parameter 15-01 Running Hours).
15-08 Number of Starts
Range: Function:
0* [0 -
2147483647 ]
NOTICE
This parameter is reset when
resetting parameter 15-07 Reset
Running Hours Counter.
This is a readout parameter only.
The counter shows the number of
starts and stops caused by a normal
start/stop command and/or when
entering/leaving sleep mode.
3.15.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (parameter 15-10 Logging Source) at individual rates
(parameter 15-11 Logging Interval). A trigger event
(parameter 15-12 Trigger Event) and window
(parameter 15-14 Samples Before Trigger) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to be
logged.
[0] * None
[15] Readout:
actual setup
[1397] Alert Alarm
Word
[1398] Alert Warning
Word
[1399] Alert Status
Word
[1600] Control Word
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 157