15-10 Logging Source
Array [4]
Option: Function:
[1860] Digital Input 2
[3110] Bypass Status
Word
15-11 Logging Interval
Array [4]
Range: Function:
Size
related*
[ 0.000 -
0.000 ]
Enter the interval in ms between
each sampling of the variables to
be logged.
15-12 Trigger Event
Option: Function:
Selects the trigger event. When the
trigger event occurs, a window is
applied to freeze the log. The log
then retains a specied percentage
of samples before the occurrence of
the trigger event
(parameter 15-14 Samples Before
Trigger).
[0] * False
[1] True
[2] Running
[3] In range
[4] On reference
[5] Torque limit
[6] Current Limit
[7] Out of current
range
[8] Below I low
[9] Above I high
[10] Out of speed
range
[11] Below speed
low
[12] Above speed
high
[13] Out of feedb.
range
[14] Below feedb.
low
[15] Above feedb.
high
[16] Thermal
warning
[17] Mains out of
range
[18] Reversing
[19] Warning
[20] Alarm (trip)
15-12 Trigger Event
Option: Function:
[21] Alarm (trip
lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[33] Digital input
DI18
[34] Digital input
DI19
[35] Digital input
DI27
[36] Digital input
DI29
[37] Digital input
DI32
[38] Digital input
DI33
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
15-13 Logging Mode
Option: Function:
[0] * Log always Select [0] Log always for continuous
logging.
[1] Log once on
trigger
Select [1] Log once on trigger to
start and stop logging conditionally
using parameter 15-12 Trigger Event
and parameter 15-14 Samples Before
Trigger.
15-14 Samples Before Trigger
Range: Function:
50* [0 - 100 ] Enter the percentage of all samples
to be retained in the log before a
trigger event occurs. See also
parameter 15-12 Trigger Event and
parameter 15-13 Logging Mode.
3.15.3 15-2* Historic Log
View up to 50 logged data items via the array parameters
in this parameter group. Data is logged every time an
event occurs (not to be confused with SLC events). Events
in this context are dened as a change in 1 of the
following areas:
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 159
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals