EasyManuals Logo
Home>Danfoss>DC Drives>vlt FC 102

Danfoss vlt FC 102 Programming Guide

Danfoss vlt FC 102
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #115 background imageLoading...
Page #115 background image
3.8.7 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4–20 mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Same options and functions as parameter 6-50 Terminal 42
Output.
6-61 Terminal X30/8 Min. Scale
Range: Function:
0 %* [0 - 200 %] Scales the minimum output of the
selected analog signal on terminal
X30/8. Scale the minimum value as
a percentage of the maximum
signal value. For example, enter the
value 25% if the output should be
0 mA at 25% of the maximum
output value. The value can never
exceed the corresponding setting in
parameter 6-62 Terminal X30/8 Max.
Scale if the value is below 100%.
This parameter is active when VLT
®
General Purpose I/O MCB 101 is
mounted in the frequency
converter.
6-62 Terminal X30/8 Max. Scale
Range: Function:
100 %* [0 - 200 %] Scales the maximum output of the
selected analog signal on terminal
X30/8. Scale the value to the
required maximum value of the
current signal output. Scale the
output to give a lower current than
20 mA at full scale, or 20 mA at an
output below 100% of the
maximum signal value. If 20 mA is
the required output current at a
value between 0–100% of the full-
scale output, program the
percentage value in the parameter,
that is 50%=20 mA. If a current 4–
20 mA is required at maximum
output (100%), calculate the
percentage value as follows:
20mA/desiredmaximumcurrent × 100 %
i . e . 10mA:
20mA
10mA
× 100 % = 200 %
6-63 Terminal X30/8 Output Bus Control
Range: Function:
0 %* [0 - 100 %] Contains the value to apply to the
output terminal when it is
congured as bus-controlled.
6-64 Terminal X30/8 Output Timeout Preset
Range: Function:
0 %* [0 - 100 %] Contains the value to apply to the
output terminal when it is
congured as bus-controlled
timeout and timeout is detected.
3.9 Parameters: 8-** Main Menu -
Communications and Options
3.9.1 8-0* General Settings
8-01 Control Site
The setting in this parameter overrides the settings in
parameter 8-50 Coasting Select to parameter 8-56 Preset Reference
Select.
Option: Function:
[0] Digital and
ctrl.word
Use both digital input and control
word.
[1] Digital only Use digital inputs only.
[2] Controlword
only
Use control word only.
8-02 Control Source
Select the source of the control word: 1 of 2 serial interfaces, or
4 installed options. During initial power-up, the frequency
converter automatically sets this parameter to [3] Option A if it
detects a valid eldbus option installed in slot A. If the option is
removed, the frequency converter detects a change in the
conguration, sets parameter 8-02 Control Source back to default
setting [1] FC Port, and the frequency converter trips. If an option
is installed after initial power-up, the setting of
parameter 8-02 Control Source does not change but the
frequency converter trips and shows alarm 67, Option Changed.
Option: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
[0] None
[1] FC Port
[2] USB Port
[3] Option A
[4] Option B
[5] Option C0
[6] Option C1
[30] External Can
8-03 Control Timeout Time
Range: Function:
Size
related*
[0.5 - 18000
s]
Enter the maximum time expected
to pass between the reception of 2
consecutive telegrams. If this time
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 113
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals