11-21 Store Data Values
Option: Function:
[2] Store all
setups
3.13 Parameters: 13-** Main Menu - Smart
Logic
3.13.1 13-** Prog. Features
Smart logic control (SLC) is a sequence of user-dened
actions (see parameter 13-52 SL Controller Action [x])
executed by the SLC when the associated user-dened
event (see parameter 13-51 SL Controller Event [x]) is
evaluated as true by the SLC. Events and actions are each
numbered and linked together in pairs. This means that
when [0] event is fullled (attains the value true), [0] action
is executed. After this, the conditions of [1] event are
evaluated and if evaluated true, [1] action is executed and
so on. Only 1 event is evaluated at any time. If an event is
evaluated as false, nothing happens (in the SLC) during the
current scan interval and no other events are evaluated.
This means that when the SLC starts, it evaluates [0] event
(and only [0] event) at each scan interval. Only when [0]
event is evaluated true, the SLC executes [0] action and
starts evaluating [1] event. It is possible to program from 1
to 20 events and actions.
When the last event/action has been executed, the
sequence starts over again from [0] event/[0] action.
Illustration 3.35 shows an example with 3 events/actions.
130BA062.14
State 1
13-51.0
13-52.0
State 2
13-51.1
13-52.1
Start
event P13-01
State 3
13-51.2
13-52.2
State 4
13-51.3
13-52.3
Stop
event P13-02
Stop
event P13-02
Stop
event P13-02
Illustration 3.35 Example with 3 Events/Actions
Starting and stopping the SLC
Start and stop the SLC by selecting [1] On or [0] O in
parameter 13-00 SL Controller Mode. The SLC always starts
in state 0 (where it evaluates [0] event). The SLC starts
when the start event (dened in parameter 13-01 Start
Event) is evaluated as true (provided that [1] On is selected
in parameter 13-00 SL Controller Mode). The SLC stops when
the stop event (parameter 13-02 Stop Event) is true.
Parameter 13-03 Reset SLC resets all SLC parameters and
starts programming from scratch.
3.13.2 13-0* SLC Settings
Use the SLC settings to activate, deactivate, and reset the
smart logic control sequence. The logic functions and
comparators are always running in the background, which
opens for separate control of digital inputs and outputs.
13-00 SL Controller Mode
Option: Function:
[0] O Disables the smart logic controller.
[1] On Enables the smart logic controller.
13-01 Start Event
Option: Function:
Select the boolean (true or false)
input to activate smart logic
control.
[0] False Enters the xed value of false in the
logic rule.
[1] True Enters the xed value of true in the
logic rule.
[2] Running See parameter group 5-3* Digital
Outputs for further description.
[3] In range See parameter group 5-3* Digital
Outputs for further description.
[4] On reference See parameter group 5-3* Digital
Outputs for further description.
[5] Torque limit See parameter group 5-3* Digital
Outputs for further description.
[6] Current Limit See parameter group 5-3* Digital
Outputs for further description.
[7] Out of current
range
See parameter group 5-3* Digital
Outputs for further description.
[8] Below I low See parameter group 5-3* Digital
Outputs for further description.
[9] Above I high See parameter group 5-3* Digital
Outputs for further description.
[10] Out of speed
range
[11] Below speed
low
See parameter group 5-3* Digital
Outputs for further description.
[12] Above speed
high
See parameter group 5-3* Digital
Outputs for further description.
[13] Out of feedb.
range
[14] Below feedb.
low
[15] Above feedb.
high
[16] Thermal
warning
See parameter group 5-3* Digital
Outputs for further description.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
126 Danfoss A/S © 10/2019 All rights reserved. M0010001
33