16-96 Maintenance Word
Range: Function:
The 2
nd
digit 4 refers to the 3
rd
row
indicating that the frequency
converter cooling fan requires
maintenance.
The 3
rd
digit 0 indicates that no
items from the 2
nd
row require
maintenance.
The 4
th
digit A refers to the top row
indicating that the valve and the
pump bearings require
maintenance.
3.17 Parameters: 18-** Main Menu - Data
Readouts 2
3.17.1 18-0* Maintenance Log
This group contains the last 10 preventive maintenance
events. Maintenance log 0 is the latest and maintenance
log 9 the oldest.
By selecting 1 of the logs and pressing [OK], the
maintenance item, action, and time of the occurrence are
shown in parameter 18-00 Maintenance Log: Item
parameter 18-03 Maintenance Log: Date and Time.
The alarm log key allows access to both alarm log and
maintenance log.
18-00 Maintenance Log: Item
Array [10]
Shows the fault code. For information about the fault code, see
the design guide.
Range: Function:
0* [0 - 255 ] Find the meaning of the
maintenance item in
parameter 23-10 Maintenance Item.
18-01 Maintenance Log: Action
Array [10]
Shows the fault code. For information about the fault code, see
the design guide.
Range: Function:
0* [0 - 255 ] Find the meaning of the
maintenance action in
parameter 23-11 Maintenance Action.
18-02 Maintenance Log: Time
Array [10]
Range: Function:
0 s* [0 -
2147483647 s]
Shows when the logged event
occurred. Time is measured in s
since last power-up.
18-03 Maintenance Log: Date and Time
Array [10]
Range: Function:
Size
related*
[ 0 - 0 ] Shows when the logged event
occurred.
NOTICE
This requires that the date and
time is programmed in
parameter 0-70 Date and Time.
Date format depends on the setting
in parameter 0-71 Date Format,
while the time format depends on
the setting in parameter 0-72 Time
Format.
NOTICE
The frequency converter has
no back-up of the clock
function. The set date/time
resets to default (2000-01-01
00:00) after a power-down
unless a real-time clock
module with back-up is
installed. In
parameter 0-79 Clock Fault, it is
possible to program a warning
in case the clock has not been
set properly, for example after
a power-down. Incorrect
setting of the clock aects the
time stamps for the
maintenance events.
NOTICE
When mounting a VLT
®
Analog I/O MCB 109 option card,
a battery back-up of date and time is included.
3.17.2 18-1* Fire Mode Log
The log covers the latest 10 faults which have been
suppressed by the re mode function. See parameter group
24-0*, Fire Mode. The log can be viewed either via the
below parameters or by pressing [Alarm Log] on the LCP
and select Fire mode log. It is not possible to reset the re
mode log.
18-10 FireMode Log:Event
Range: Function:
0* [0 - 255 ] This parameter contains an array
with 10 elements. The number read
represents a fault code, which
corresponds to a specic alarm. This
can be found in the chapter
Troubleshooting in the design guide.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 171
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals