22-60 Broken Belt Function
Selects the action to be performed if the broken-belt condition is
detected.
Option: Function:
NOTICE
Do not set
parameter 14-20 Reset Mode to
[13] Innite auto reset when
parameter 22-60 Broken Belt
Function is set to [2] Trip.
Doing so causes the frequency
converter to continuously cycle
between running and stopping
when a broken-belt condition
is detected.
NOTICE
For frequency converters with
constant-speed bypass.
If an automatic bypass
function starts the bypass at
persistent alarm conditions,
disable the bypass’s automatic
bypass function if [2] Alarm or
[3] Man. Reset Alarm is selected
as the broken-belt function.
[0] * O
[1] Warning The frequency converter continues
to run, but activates a broken-belt
warning (warning 95, Broken belt). A
frequency converter digital output
or a serial communication bus can
communicate a warning to other
equipment.
[2] Trip The frequency converter stops
running and activates a broken-belt
alarm (alarm 95, Broken belt). A
frequency converter digital output
or a serial communication bus can
communicate an alarm to other
equipment.
22-61 Broken Belt Torque
Range: Function:
10 %* [0 - 100 %] Sets the broken-belt torque as a
percentage of the rated motor
torque.
22-62 Broken Belt Delay
Range: Function:
10 s [0 - 600 s] Sets the time for which the broken
belt conditions must be active
before carrying out the action
22-62 Broken Belt Delay
Range: Function:
selected in parameter 22-60 Broken
Belt Function.
3.20.6 22-7* Short Cycle Protection
When controlling refrigeration compressors, often there is a
need for limiting the numbers of starts. One way to do this
is to ensure a minimum run time (time between a start
and a stop) and a minimum interval between starts.
This means that any normal stop command can be
overridden by the minimum run time function
(parameter 22-77 Minimum Run Time) and any normal start
command (start/jog/freeze) can be overridden by the
interval between starts function (parameter 22-76 Interval
between Starts).
None of the 2 functions are active if hand-on or o modes
have been activated via the LCP. If selecting hand-on or
o, the 2 timers are reset to 0, and do not start counting
until Auto is pressed and an active start command applied.
NOTICE
A coast command or missing run permissive signal
override both minimum run time and interval between
starts functions.
22-75 Short Cycle Protection
Option: Function:
[0] * Disabled Timer set in parameter 22-76 Interval
between Starts is disabled.
[1] Enabled Timer set in parameter 22-76 Interval
between Starts is enabled.
22-76 Interval between Starts
Range: Function:
Size
related*
[ par. 22-77 -
3600 s]
Sets the minimum time between 2
starts. Any normal start command
(start/jog/freeze) is disregarded until
the timer has expired.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
208 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals