22-26 Dry Pump Function
Select the action for dry-pump operation.
Option: Function:
or a serial communication bus can
communicate a warning to other
equipment.
[2] Alarm The frequency converter stops
running and activates a dry-pump
alarm (alarm 93, Dry pump). A
frequency converter digital output
or a serial communication bus can
communicate an alarm to other
equipment.
[3] Man. Reset
Alarm
The frequency converter stops
running and activates a dry-pump
alarm (alarm 93, Dry pump). A
frequency converter digital output
or a serial communication bus can
communicate an alarm to other
equipment.
[4] Stop and Trip
22-27 Dry Pump Delay
Range: Function:
10 s* [0 - 600 s] Denes for how long the dry-pump
condition must be active before
activating a warning or an alarm.
The frequency converter waits for
the no-ow delay time
(parameter 22-24 No-Flow Delay) to
expire before the timer for the dry-
pump delay starts.
3.20.2 22-3* No-ow Power Tuning
NOTICE
Set parameter 1-03 Torque Characteristics before tuning
takes place.
If auto set-up is disabled in parameter 22-20 Low Power
Auto Set-up, the tuning sequence is:
1. Close the main valve to stop ow.
2. Run with motor until the system has reached
normal operating temperature.
3. Press [Hand On] and adjust speed for approxi-
mately 85% of rated speed. Note the exact speed.
4. Read power consumption either by looking for
actual power in the data line in the LCP or by
viewing 1 of the following parameters:
4a Parameter 16-10 Power [kW].
Or
4b Parameter 16-11 Power [hp] in the Main
Menu.
Note the power readout.
5. Change speed to approximately 50% of rated
speed. Note the exact speed.
6. Read power consumption either by looking for
actual power in the data line in the LCP or by
viewing 1 of the following parameters:
6a Parameter 16-10 Power [kW].
Or
6b Parameter 16-11 Power [hp] in the Main
Menu.
Note the power readout.
7. Program the speeds used in:
7a Parameter 22-32 Low Speed [RPM].
7b Parameter 22-33 Low Speed [Hz].
7c Parameter 22-36 High Speed [RPM].
7d Parameter 22-37 High Speed [Hz].
8. Program the associated power values in:
8a Parameter 22-34 Low Speed Power [kW].
8b Parameter 22-35 Low Speed Power [HP].
8c Parameter 22-38 High Speed Power [kW].
8d Parameter 22-39 High Speed Power [HP].
9. Switch back with [Auto On] or [Oîš„].
22-30 No-Flow Power
Range: Function:
0 kW* [0 - 0 kW] Readout of calculated no-ow
power at actual speed. If power
drops to the display value, the
frequency converter considers the
condition as a no-ow situation.
22-31 Power Correction Factor
Range: Function:
100 %* [1 - 400 %] Make corrections to the calculated
power in parameter 22-30 No-Flow
Power.
If no-ow is detected when it
should not be detected, decrease
the setting. However, if no-ow is
not detected when it should be
detected, increase the setting to
above 100%.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
202 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals