3.9.9 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
xed jog speed via the serial port
or eldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
xed jog speed via the serial port
or eldbus option.
8-94 Bus Feedback 1
Range: Function:
0* [-200 - 200 ] Write feedback to this parameter
via the serial communication port
or eldbus option. Select this
parameter as a feedback source in
parameter 20-00 Feedback 1 Source,
parameter 20-03 Feedback 2 Source,
or parameter 20-06 Feedback 3
Source.
8-95 Bus Feedback 2
Range: Function:
0* [-200 - 200 ] See parameter 8-94 Bus Feedback 1
for further details.
8-96 Bus Feedback 3
Range: Function:
0* [-200 - 200 ] See parameter 8-94 Bus Feedback 1
for further details.
3.10 Parameters: 9-** Main Menu -
PROFIBUS
Parameters in this section are only visible with the VLT
®
PROFIBUS DP MCA 101 option installed.
For PROFIBUS parameter descriptions, see the VLT
®
PROFIBUS DP MCA 101 Programming Guide.
3.11
Parameters: 10-** Main Menu - CAN
Fieldbus
For DeviceNet parameter descriptions, see the DeviceNet
Operating Instructions.
3.12
Parameters: 11-** Main Menu -
LonWorks
Parameter group for all LonWorks specic parameters.
Parameters related to LonWorks ID.
11-00 Neuron ID
Range: Function:
0* [0 - 0 ] View the Neuron chip's unique
Neuron ID number.
11-10 Drive Prole
Option: Function:
This parameter allows selecting
between LONMARK functional
proles.
[0] * VSD prole The Danfoss Prole and the Node
Object are common for all proles.
11-15 LON Warning Word
Range: Function:
0* [0 - 65535 ] This parameter contains the LON
specic warnings.
Bit Status
0 Internal fault
1 Internal fault
2 Internal fault
3 Internal fault
4 Internal fault
5 Reserved
6 Reserved
7 Reserved
8 Reserved
9 Changeable types
10 Initialisation error
11 Internal communication error
12 Software revision mismatch
13 Bus not active
14 Option not present
15 LON input (nvi/nci) exceeds limits
Table 3.18 LON Warning Word
11-17 XIF Revision
Range: Function:
0* [0 - 5 ] This parameter contains the version
of the external interface le on the
Neuron C chip on the LON option.
11-18 LonWorks Revision
Range: Function:
0* [0 - 5 ] This parameter contains the
software version of the application
program on the Neuron C chip on
the LON option.
11-21 Store Data Values
Option: Function:
[0] * O
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 125