y-axis: I
m
/I
m,n
x 100 [%]
Parameter 1-98 ATEX ETR interpol.
points freq.
Parameter 1-99 ATEX ETR
interpol points current
[0]=5 Hz [0]=40%
[1]=15 Hz [1]=80%
[2]=25 Hz [2]=100%
[3]=50 Hz [3]=100%
Table 3.10 Interpolation Points
All operating points underneath the curve are allowed
continuously. Above the line, however, these are only
allowed for a limited time calculated as a function of the
overload. If a machine current is greater than 1.5 times the
rated current, shutdown is immediate.
1-99 ATEX ETR interpol points current
Only visible if parameter 1-90 Motor Thermal Protection is set to
[20] or [21].
Range: Function:
Size
related*
[0 - 100 %] Denition of thermal limitation
curve. For example, see
parameter 1-98 ATEX ETR interpol.
points freq.
Use the 4 current points [A] from the motor nameplate.
Calculate the values as percentage of nominal motor
current, I
m
/I
m,n
x 100 [%], and enter into this array.
Together with parameter 1-98 ATEX ETR interpol. points freq.,
these constitute a table (f [Hz],I [%]).
NOTICE
All frequency/current limit points from the motor
nameplate or motor datasheet must be programmed.
3.4 Parameters: 2-** Main Menu - Brakes
3.4.1 2-0* DC brakes
Parameter group for conguring the DC brake and DC hold
functions.
2-00 DC Hold/Preheat Current
Range: Function:
50 %* [ 0 - 160 %]
NOTICE
Parameter 2-00 DC Hold/
Preheat Current has no eect
when parameter 1-10 Motor
Construction=[1] PM, non-
salient SPM.
2-00 DC Hold/Preheat Current
Range: Function:
NOTICE
The maximum value depends
on the rated motor current.
Avoid 100% current for too
long. It may damage the
motor.
Enter a value for holding current as
a percentage of the rated motor
current I
M,N
set in
parameter 1-24 Motor Current. 100%
DC hold current corresponds to I
M,N
.
This parameter holds the motor
(holding torque) or preheats the
motor.
This parameter is active if [1] DC
hold/Motor Preheat is selected in
parameter 1-80 Function at Stop.
2-01 DC Brake Current
Range: Function:
50 %* [ 0 - 1000 %]
NOTICE
The maximum value depends
on the rated motor current.
Avoid 100% current for too
long. It may damage the
motor.
Enter a value for current as a
percentage of the rated motor
current I
M,N
, see
parameter 1-24 Motor Current. 100%
DC brake current corresponds to
I
M,N
.
DC brake current is applied on a
stop command, when the speed is
lower than the limit set in:
Parameter 2-03 DC Brake
Cut In Speed [RPM].
Parameter 2-04 DC Brake
Cut In Speed [Hz], when
the DC brake inverse
function is active, or via
the serial communication
port.
The braking current is active during
the time period set in
parameter 2-02 DC Braking Time.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
70 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals