2-02 DC Braking Time
Range: Function:
10 s* [0 - 60 s] Set the duration of the DC brake
current set in parameter 2-01 DC
Brake Current, once activated.
2-03 DC Brake Cut In Speed [RPM]
Range: Function:
Size
related*
[ 0 - 0 RPM] Set the DC brake cut-in speed for
activation of the DC braking current
set in parameter 2-01 DC Brake
Current, upon a stop command.
When parameter 1-10 Motor
Construction is set to [1] PM non-
salient SPM, this value is limited to
0 RPM (OFF).
2-04 DC Brake Cut In Speed [Hz]
Range: Function:
Size
related*
[ 0 - 0.0 Hz] This parameter is for setting the DC
brake cut-in speed at which the DC
braking current (parameter 2-01 DC
Brake Current) is to be active in
connection with a stop command.
2-06 Parking Current
Range: Function:
50 %* [ 0 - 1000 %]
NOTICE
Parameter 2-06 Parking Current
and parameter 2-07 Parking
Time: Only active if [1] PM,
non-salient SPM is selected in
parameter 1-10 Motor
Construction.
Set current as percentage of rated
motor current, parameter 1-24 Motor
Current. Active with
parameter 1-73 Flying Start. The
parking current is active during the
time period set in
parameter 2-07 Parking Time.
2-07 Parking Time
Range: Function:
3 s* [0.1 - 60 s] Set the duration of the parking
current time set in
parameter 2-06 Parking Current.
Active with parameter 1-73 Flying
Start.
2-07 Parking Time
Range: Function:
NOTICE
Parameter 2-07 Parking Time is
only active when [1] PM, non-
salient SPM is selected in
parameter 1-10 Motor
Construction.
3.4.2 2-1* Brake Energy Funct.
Parameter group for selecting dynamic brake parameters.
Only valid for frequency converters with brake chopper.
2-10 Brake Function
Option: Function:
Available options depend on
parameter 1-10 Motor Construction:
[0] Asynchron:
[0] O
[1] Resistor brake
[2] AC brake
[1] PM non-salient:
[0] O
[1] Resistor brake
[0] O No brake resistor installed.
[1] Resistor brake Brake resistor incorporated in the
system for dissipation of excess
brake energy as heat. Connecting a
brake resistor allows a higher DC-
link voltage during braking
(generating operation). The resistor
brake function is only active in
frequency converters with an
integral dynamic brake.
[2] AC brake AC brake only works in compressor
torque mode in
parameter 1-03 Torque Character-
istics.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 71
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals