35-46 Term. X48/2 Filter Time Constant
Range: Function:
0.005 s* [0.005 - 10 s] Enter the lter time constant. This is
a rst-order digital low-pass lter
time constant for suppressing
electrical noise in terminal X48/2. A
high time constant value improves
dampening but also increases the
time delay through the lter.
35-47 Term. X48/2 Live Zero
Option: Function:
[0] Disabled
[1] * Enabled
3.29 Parameters: 36-** Programmable I/O
Option
Parameters for conguring VLT
®
Programmable I/O .
Parameters in this group are active only when VLT
®
Programmable I/O is installed.
3.29.1 36-0* I/O Mode
Use the parameters in this group to congure the mode of
inputs and outputs of VLT
®
Programmable I/O .
Terminals can be programmed to provide voltage, current,
or digital output.
36-00 Terminal X49/1 Mode
Option: Function:
Select the mode of analog terminal
X49/1.
[0] Current
[1] * Voltage
[2] Pt 1000 [°C]
1000 Ω at 0°C
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
1000 Ω at 0°C
[5] Ni 1000 [°F]
36-01 Terminal X49/3 Mode
Option: Function:
Select the mode of analog terminal
X49/3.
[0] Current
[1] * Voltage
[2] Pt 1000 [°C]
1000 Ω at 0°C
[3] Pt 1000 [°F]
1000 Ω at 0°F
[4] Ni 1000 [°C]
1000 Ω at 0°C
[5] Ni 1000 [°F]
1000 Ω at 0°F
36-02 Terminal X49/5 Mode
Option: Function:
Select the mode of analog terminal
X49/5.
[0] Current
[1] * Voltage
[2] Pt 1000 [°C]
1000 Ω at 0°C
[3] Pt 1000 [°F]
[4] Ni 1000 [°C]
1000 Ω at 0°C
[5] Ni 1000 [°F]
36-03 Terminal X49/7 Mode
Select the output mode of analog terminal X49/7.
Option: Function:
[0] * Voltage 0-10V
[1] Voltage 2-10V
[2] Current
0-20mA
[3] Current
4-20mA
[4] Digital
36-04 Terminal X49/9 Mode
Select the output mode of analog terminal X49/9.
Option: Function:
[0] * Voltage 0-10V
[1] Voltage 2-10V
[2] Current
0-20mA
[3] Current
4-20mA
[4] Digital
36-05 Terminal X49/11 Mode
Select the output mode of analog terminal X49/11.
Option: Function:
[0] * Voltage 0-10V
[1] Voltage 2-10V
[2] Current
0-20mA
[3] Current
4-20mA
[4] Digital
3.29.2 36-1* Analog Input X49/1
36-10 Terminal X49/1 Low Voltage
Range: Function:
0.07 V* [ 0 - par.
36-12 V]
Enter the voltage that corresponds
to the low reference value in
parameter 36-14 Term. X49/1 Low
Ref./Feedb. Value.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
262 Danfoss A/S © 10/2019 All rights reserved. M0010001