3.15.7 15-9* Parameter Info
15-92 Dened Parameters
Range: Function:
0* [0 - 9999 ] View a list of all dened parameters
in the frequency converter. The list
ends with 0.
15-93 Modied Parameters
Range: Function:
0* [0 - 9999 ] View a list of the parameters that
have been changed from their
default setting. The list ends with 0.
Changes may not be visible until
up to 30 s after implementation.
15-98 Drive Identication
Range: Function:
0* [0 - 40 ] This parameter contains data used
by the MCT 10 Set-up Software.
15-99 Parameter Metadata
Array [30]
Range: Function:
0* [0 - 9999 ] This parameter contains data used
by the MCT 10 Set-up Software
tool.
3.16 Parameters: 16-** Main Menu - Data
Readouts
3.16.1 16-0* General Status
16-00 Control Word
Range: Function:
0* [0 - 65535 ] View the control word sent from
the frequency converter via the
serial communication port in hex
code.
16-01 Reference [Unit]
Range: Function:
0 Referen-
ceFeedback
Unit*
[-999999 -
999999
Reference-
FeedbackUnit]
View the present reference value
applied on impulse or analog basis
in the unit resulting from the
conguration selected in
parameter 1-00 Conguration Mode
(Hz, Nm, or RPM).
16-02 Reference [%]
Range: Function:
0 %* [-200 -
200 %]
View the total reference. The total
reference is the sum of digital,
16-02 Reference [%]
Range: Function:
analog, preset, bus, and freeze
references, plus catch up and slow
down.
16-03 Status Word
Range: Function:
0* [0 - 65535 ] View the status word sent from the
frequency converter via the serial
communication port in hex code.
16-05 Main Actual Value [%]
Range: Function:
0 %* [-100 -
100 %]
View the 2-byte word sent with the
status word to the eldbus master
reporting the main actual value.
16-09 Custom Readout
Range: Function:
0 Custom-
ReadoutUni
t*
[-999999.99 -
999999.99
CustomRea-
doutUnit]
View the user-dened readouts as
dened in parameter 0-30 Custom
Readout Unit,
parameter 0-31 Custom Readout Min
Value, and parameter 0-32 Custom
Readout Max Value.
3.16.2 16-1* Motor Status
16-10 Power [kW]
Range: Function:
0 kW* [0 - 10000
kW]
Shows motor power in kW. The
value shown is calculated based on
the actual motor voltage and motor
current. The value is ltered, and
therefore approximately 1.3 s may
pass from when an input value
changes to when the data readout
values change. The resolution of
readout value on eldbus is in
10 W steps.
16-11 Power [hp]
Range: Function:
0 hp* [0 - 10000
hp]
View the motor power in hp. The
value shown is calculated based on
the actual motor voltage and motor
current. The value is ltered, and
therefore approximately 1.3 ms may
pass from when an input value
changes to when the data readout
values change.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 163
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals