The condition for dry-pump signal:
Power consumption below no-ow level.
and
Pump running at maximum speed or maximum reference open loop, whichever is lowest.
The signal must be active for a set time (parameter 22-27 Dry Pump Delay) before the selected action takes place.
Possible actions to select (parameter 22-26 Dry Pump Function):
Warning
Alarm
Enable and commission
no-ow detection in parameter 22-23 No-Flow Function and parameter group 22-3* No-Flow Power
Tuning.
22-20 Low Power Auto Set-up
Start of auto set-up of power data for no-ow power tuning.
Option: Function:
[0] * O
[1] Enabled
NOTICE
Do the auto set-up when the
system has reached normal
operating temperature.
NOTICE
It is important that
parameter 4-13 Motor Speed
High Limit [RPM] or
parameter 4-14 Motor Speed
High Limit [Hz] is set to the
maximum operational speed of
the motor.
It is important to do the auto
set-up before conguring the
integrated PI controller as
settings are reset when
changing from closed loop to
open loop in
parameter 1-00 Conguration
Mode.
NOTICE
Carry out the tuning with the
same settings in
parameter 1-03 Torque Charac-
teristics as for operation after
the tuning.
An auto set-up sequence is
activated, automatically setting the
speed to approximately 50% and
85% of nominal motor speed
(parameter 4-13 Motor Speed High
Limit [RPM], parameter 4-14 Motor
22-20 Low Power Auto Set-up
Start of auto set-up of power data for no-ow power tuning.
Option: Function:
Speed High Limit [Hz]). At those 2
speeds, the power consumption is
automatically measured and stored.
Before enabling auto set-up:
1. Close valves to create a
no-ow condition.
2. Set the frequency
converter to open loop
(parameter 1-00 Congu-
ration Mode).
It is important also to set
parameter 1-03 Torque
Characteristics.
22-21 Low Power Detection
Option: Function:
[0] * Disabled
[1] Enabled To set the parameters in parameter
group 22-3* No-Flow Power Tuning
for proper operation, carry out the
low-power detection commis-
sioning.
22-22 Low Speed Detection
Option: Function:
[0] * Disabled
[1] Enabled Detects when the motor operates
with a speed as set in
parameter 4-11 Motor Speed Low
Limit [RPM] or parameter 4-12 Motor
Speed Low Limit [Hz].
Parameter Descriptions
VLT
®
HVAC Drive FC 102
200 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals