18-11 Fire Mode Log: Time
Range: Function:
0 s* [0 -
2147483647 s]
This parameter contains an array
with 10 elements. The parameter
shows when the logged event
occurred. Time is measured in
seconds since the 1
st
start of the
motor.
18-12 Fire Mode Log: Date and Time
Range: Function:
Size
related*
[ 0 - 0 ] This parameter contains an array
with 10 elements. The parameter
shows at which date and time the
logged event occurred. The
function relies on the fact that the
actual date and time has been set
in parameter 0-70 Date and Time.
NOTICE
There is no built-in battery
back-up of the clock. Use an
external back-up, for example
the one in the VLT
®
Analog I/O
MCB 109 Analog I/O option
card See parameter group 0-7*
Clock Settings.
3.17.3 18-3* Analog I/O
Parameters for reporting the digital and analog I/O ports.
18-30 Analog Input X42/1
Range: Function:
0* [-20 - 20 ] Readout of the value of the signal
applied to terminal X42/1 on the
analog I/O card.
The units of the value shown in the
LCP correspond to the mode
selected in parameter 26-00 Terminal
X42/1 Mode.
18-31 Analog Input X42/3
Range: Function:
0* [-20 - 20 ] Readout of the value of the signal
applied to terminal X42/3 on the
analog I/O card.
The units of the value shown in the
LCP correspond to the mode
selected in parameter 26-01 Terminal
X42/3 Mode.
18-32 Analog Input X42/5
Range: Function:
0* [-20 - 20 ] Readout of the value of the signal
applied to terminal X42/5 on the
analog I/O card.
The units of the value shown in the
LCP correspond to the mode
selected in parameter 26-02 Terminal
X42/5 Mode.
18-33 Analog Out X42/7 [V]
Range: Function:
0* [0 - 30 ] Readout of the value of the signal
applied to terminal X42/7 on the
analog I/O card.
The value shown reects the
selection in
parameter 26-40 Terminal X42/7
Output.
18-34 Analog Out X42/9 [V]
Range: Function:
0* [0 - 30 ] Readout of the value of the signal
applied to terminal X42/9 on the
analog I/O card.
The value shown reects the
selection in
parameter 26-50 Terminal X42/9
Output.
18-35 Analog Out X42/11 [V]
Range: Function:
0* [0 - 30 ] Readout of the value of the signal
applied to terminal X42/11 on the
analog I/O card.
The value shown reects the
selection in
parameter 26-60 Terminal X42/11
Output.
18-36 Analog Input X48/2 [mA]
Range: Function:
0* [-20 - 20 ] View the actual current measured
at input X48/2.
18-37 Temp. Input X48/4
Range: Function:
0* [-500 - 500 ] View the actual temperature
measured at input X48/4. The
temperature unit is based on the
selection in parameter 35-00 Term.
X48/4 Temperature Unit.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
172 Danfoss A/S © 10/2019 All rights reserved. M0010001
33

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals