26-36 Term. X42/5 Filter Time Constant
Range: Function:
0.005 s* [0.005 - 10 s]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
This is a rst-order digital low-pass
lter time constant for suppressing
noise in terminal X42/5. A high
time constant value improves
dampening, but also increases the
time delay through the lter.
26-37 Term. X42/5 Live Zero
Option: Function:
Enable or disable the live zero
monitoring.
[0] Disabled
[1] * Enabled
3.24.5 26-4* Analog Out X42/7
Parameters for conguring the scaling and output function
for analog output, terminal X42/7.
26-40 Terminal X42/7 Output
Option: Function:
Set the function of terminal X42/7
as an analog current output.
[0] * No operation
[52] MCO 0-20mA/
0-10V
[86] Pressure
Sensor 1
[88] Pressure
Sensor 2
[93] Pressure
Sensor 3
[100] Output freq.
0-100
0–100 Hz, (0–10 V).
[101] Reference
Min-Max
Minimum reference–maximum
reference, (0–10 V).
[102] Feedback
+-200%
-200% to +200% of
parameter 3-03 Maximum Reference,
(0–10 V).
[103] Motor cur. 0-
Imax
0–inverter maximum current
(parameter 16-37 Inv. Max. Current),
(0–10 V).
[104] Torque 0-Tlim 0–torque limit
(parameter 4-16 Torque Limit Motor
Mode), (0–10 V).
26-40 Terminal X42/7 Output
Option: Function:
[105] Torque 0-
Tnom
0–motor rated torque, (0–10 V).
[106] Power 0-Pnom 0–motor rated power, (0–10 V).
[107] Speed 0-
HighLim
0–speed high limit
(parameter 4-13 Motor Speed High
Limit [RPM] and
parameter 4-14 Motor Speed High
Limit [Hz]), (0–10 V).
[113] Ext. Closed
Loop 1
0–100%, (0–10 V).
[114] Ext. Closed
Loop 2
0–100%, (0–10 V).
[115] Ext. Closed
Loop 3
0–100%, (0–10 V).
[121] Air pres. to
Flow
[139] Bus ctrl. 0–100%, (0–10 V).
[141] Bus ctrl t.o. 0–100%, (0–10 V).
[186] Pressure
Sensor 4
26-41 Terminal X42/7 Min. Scale
Range: Function:
0 %* [0 - 200 %] Scale the minimum output of the
selected analog signal at terminal
X42/7 as a percentage of the
maximum signal level. For example,
if 0 V (or 0 Hz) is required at 25%
of the maximum output value,
program 25%. Scaling values up to
100% can never be higher than the
corresponding setting in
parameter 26-42 Terminal X42/7 Max.
Scale.
See principle graph for
parameter 6-51 Terminal 42 Output
Min Scale.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 253
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
CategoryDC Drives
ModelDanfoss VLT FC 102
Output voltage range0 to rated motor voltage
Power range0.37 kW to 200 kW
Communication interfacesRS-485
Protection featuresOvervoltage, undervoltage, overcurrent, short circuit, earth fault, overtemperature, motor thermal protection
Cooling methodAir-cooled
Enclosure ratingIP20, IP21, IP55 (depending on model)
ApprovalsCE, UL, cUL