26-52 Terminal X42/9 Max. Scale
See Illustration 3.31.
Range: Function:
100 %* [0 - 200 %] Scale the maximum output of the
selected analog signal at terminal
X42/9. Set the value to the
maximum value of the voltage
signal output. Scale the output to
give a voltage lower than 10 V at
full scale; or 10 V at an output
below 100% of the maximum signal
value. If 10 V is the required output
current at a value between 0–100%
of the full-scale output, program
the percentage value in the
parameter, that is, 50%=10 V. If a
voltage 0–10 V is required at
maximum output, calculate the
percentage as follows:
5V :
10V
5V
× 100 % = 200 %
26-53 Terminal X42/9 Bus Control
Range: Function:
0 %* [0 - 100 %] Holds the level of terminal X42/9 if
controlled by bus.
26-54 Terminal X42/9 Timeout Preset
Range: Function:
0 %* [0 - 100 %] Holds the preset level of terminal
X42/9.
If a eldbus and a timeout function
are selected in
parameter 26-60 Terminal X42/11
Output, the output presets to this
level.
3.24.7 26-6* Analog Out X42/11
Parameters for conguring the scaling and output function
for analog output, terminal X42/11.
26-60 Terminal X42/11 Output
Option: Function:
Set the function of terminal X42/11.
[0] * No operation
[52] MCO 0-20mA/
0-10V
[86] Pressure
Sensor 1
[88] Pressure
Sensor 2
[93] Pressure
Sensor 3
26-60 Terminal X42/11 Output
Option: Function:
[100] Output freq.
0-100
0–100 Hz, (0–10 V).
[101] Reference
Min-Max
Minimum reference–maximum
reference, (0–10 V).
[102] Feedback
+-200%
-200% to +200% of
parameter 3-03 Maximum Reference,
(0–10 V).
[103] Motor cur. 0-
Imax
0–inverter maximum current
(parameter 16-37 Inv. Max. Current),
(0–10 V).
[104] Torque 0-Tlim 0–torque limit
(parameter 4-16 Torque Limit Motor
Mode), (0–10 V).
[105] Torque 0-
Tnom
0–motor rated torque, (0–0 V).
[106] Power 0-Pnom 0–motor rated power, (0–10 V).
[107] Speed 0-
HighLim
0–speed high limit
(parameter 4-13 Motor Speed High
Limit [RPM] and
parameter 4-14 Motor Speed High
Limit [Hz]), (0–10 V).
[113] Ext. Closed
Loop 1
0–100%, (0–10 V).
[114] Ext. Closed
Loop 2
0–100%, (0–10 V).
[115] Ext. Closed
Loop 3
0–100%, (0–10 V).
[121] Air pres. to
Flow
[139] Bus ctrl. 0–100%, (0–10 V).
[141] Bus ctrl t.o. 0–100%, (0–10 V).
[186] Pressure
Sensor 4
26-61 Terminal X42/11 Min. Scale
For more information, see parameter 6-51 Terminal 42 Output Min
Scale.
Range: Function:
0 %* [0 - 200 %] Scale the minimum output of the
selected analog signal at terminal
X42/11 as a percentage of the
maximum signal level. For example,
if 0 V is required at 25% of the
maximum output value, program
25%. Scaling values up to 100% can
never be higher than the
corresponding setting in
parameter 26-62 Terminal X42/11
Max. Scale.
Parameter Descriptions Programming Guide