26-52 Terminal X42/9 Max. Scale
See Illustration 3.31.
Range: Function:
100 %* [0 - 200 %] Scale the maximum output of the
selected analog signal at terminal
X42/9. Set the value to the
maximum value of the voltage
signal output. Scale the output to
give a voltage lower than 10 V at
full scale; or 10 V at an output
below 100% of the maximum signal
value. If 10 V is the required output
current at a value between 0–100%
of the full-scale output, program
the percentage value in the
parameter, that is, 50%=10 V. If a
voltage 0–10 V is required at
maximum output, calculate the
percentage as follows:
5V :
10V
5V
× 100 % = 200 %
26-53 Terminal X42/9 Bus Control
Range: Function:
0 %* [0 - 100 %] Holds the level of terminal X42/9 if
controlled by bus.
26-54 Terminal X42/9 Timeout Preset
Range: Function:
0 %* [0 - 100 %] Holds the preset level of terminal
X42/9.
If a eldbus and a timeout function
are selected in
parameter 26-60 Terminal X42/11
Output, the output presets to this
level.
3.24.7 26-6* Analog Out X42/11
Parameters for conguring the scaling and output function
for analog output, terminal X42/11.
26-60 Terminal X42/11 Output
Option: Function:
Set the function of terminal X42/11.
[0] * No operation
[52] MCO 0-20mA/
0-10V
[86] Pressure
Sensor 1
[88] Pressure
Sensor 2
[93] Pressure
Sensor 3
26-60 Terminal X42/11 Output
Option: Function:
[100] Output freq.
0-100
0–100 Hz, (0–10 V).
[101] Reference
Min-Max
Minimum reference–maximum
reference, (0–10 V).
[102] Feedback
+-200%
-200% to +200% of
parameter 3-03 Maximum Reference,
(0–10 V).
[103] Motor cur. 0-
Imax
0–inverter maximum current
(parameter 16-37 Inv. Max. Current),
(0–10 V).
[104] Torque 0-Tlim 0–torque limit
(parameter 4-16 Torque Limit Motor
Mode), (0–10 V).
[105] Torque 0-
Tnom
0–motor rated torque, (0–0 V).
[106] Power 0-Pnom 0–motor rated power, (0–10 V).
[107] Speed 0-
HighLim
0–speed high limit
(parameter 4-13 Motor Speed High
Limit [RPM] and
parameter 4-14 Motor Speed High
Limit [Hz]), (0–10 V).
[113] Ext. Closed
Loop 1
0–100%, (0–10 V).
[114] Ext. Closed
Loop 2
0–100%, (0–10 V).
[115] Ext. Closed
Loop 3
0–100%, (0–10 V).
[121] Air pres. to
Flow
[139] Bus ctrl. 0–100%, (0–10 V).
[141] Bus ctrl t.o. 0–100%, (0–10 V).
[186] Pressure
Sensor 4
26-61 Terminal X42/11 Min. Scale
For more information, see parameter 6-51 Terminal 42 Output Min
Scale.
Range: Function:
0 %* [0 - 200 %] Scale the minimum output of the
selected analog signal at terminal
X42/11 as a percentage of the
maximum signal level. For example,
if 0 V is required at 25% of the
maximum output value, program
25%. Scaling values up to 100% can
never be higher than the
corresponding setting in
parameter 26-62 Terminal X42/11
Max. Scale.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 255
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals