24-91 Missing Motor Coecient 1
Range: Function:
0* [-10 - 10 ] Enter the cubic coecient of the
missing motor detection-function
multiplied by 1000.
24-92 Missing Motor Coecient 2
Range: Function:
0* [-100 - 100 ] Enter the quadratic coecient of
the missing motor detection-
function multiplied by 1000.
24-93 Missing Motor Coecient 3
Range: Function:
0* [-100 - 100 ] Enter the linear coecient of the
missing motor detection-function.
24-94 Missing Motor Coecient 4
Range: Function:
0* [-500 - 500 ] Enter the constant of the missing
motor detection-function.
24-95 Locked Rotor Function
Option: Function:
Select the action to be taken if the
motor current is above the limit
calculated as a function of the
output frequency. The function is
used for detecting for example, a
locked rotor in multi-motor
applications.
[0] * O
[1] Warning
24-96 Locked Rotor Coecient 1
Range: Function:
0* [-10 - 10 ] Enter the cubic coecient of the
locked-rotor detection function
multiplied by 1000.
24-97 Locked Rotor Coecient 2
Range: Function:
0* [-100 - 100 ] Enter the quadratic coecient of
the locked-rotor detection function
multiplied by 1000.
24-98 Locked Rotor Coecient 3
Range: Function:
0* [-100 - 100 ] Enter the linear coecient of the
locked-rotor detection function.
24-99 Locked Rotor Coecient 4
Range: Function:
0* [-500 - 500 ] Enter the constant of the locked-
rotor detection function.
Parameter Descriptions
VLT
®
HVAC Drive FC 102