WARNING/ALARM 28, Brake check failed
The brake resistor is not connected or not working.
Troubleshooting
Check parameter 2-15 Brake Check.
ALARM 29, Heat sink temp
The maximum temperature of the heat sink is exceeded.
The temperature fault is not reset until the temperature
drops below a dened heat sink temperature. The trip and
reset points are dierent based on the frequency converter
power size.
Troubleshooting
Check for the following conditions:
The ambient temperature is too high.
The motor cables are too long.
Incorrect airow clearance above and below the
frequency converter.
Blocked airow around the frequency converter.
Damaged heat sink fan.
Dirty heat sink.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the
motor is missing.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to use qualied personnel to install, start up, and
maintain the frequency converter can result in death or
serious injury.
Disconnect power before proceeding.
Troubleshooting
Remove the power from the frequency converter
and check motor phase U.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the
motor is missing.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to use qualied personnel to install, start up, and
maintain the frequency converter can result in death or
serious injury.
Disconnect power before proceeding.
Troubleshooting
Remove the power from the frequency converter
and check motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the
motor is missing.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to use qualied personnel to install, start up, and
maintain the frequency converter can result in death or
serious injury.
Disconnect power before proceeding.
Troubleshooting
Remove the power from the frequency converter
and check motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period.
Troubleshooting
Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The
eldbus on the communication option card is not
working.
WARNING/ALARM 35, Option fault
An option alarm is received. The alarm is option-specic.
The most likely cause is a power-up or a communication
fault.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the drive is lost and parameter 14-10 Mains Failure is not
set to [0] No function.
Troubleshooting
Check the fuses to the drive and mains supply to
the unit.
ALARM 37, Phase imbalance
There is a current imbalance between the power units.
ALARM 38, Internal fault
When an internal fault occurs, a code number dened in
Table 4.10 is shown.
Troubleshooting
Cycle power.
Check that the option is properly installed.
Check for loose or missing wiring.
It may be necessary to contact the Danfoss supplier or
service department. Note the code number for further
troubleshooting directions.
Troubleshooting Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 285
4 4

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals