DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming
3-118
API
Mnemonic Operands Function
Controllers
ES2/EX2/
EC5
SS2
SA2
SE
SX2
46 ANS
Timed Annunciator Set
Type
OP
Bit Devices Word devices Program Steps
X Y M S K H KnX
KnY
KnM
KnS
T C D E F
ANS: 7 steps
S
*
m
*
D
*
PULSE
16-bit
32-bit
ES2/EX2
/EC5
SS2
SA2
SE
SX2
ES2/EX2
/EC5
SS2
SA2
SE
SX2
ES2/EX2
/EC5
SS2
SA2
SE
SX2
Operands:
S: Alarm timer m: Time setting D: Alarm
Explanations:
1. ANS instruction is used to drive the output alarm device in designated time.
2. Operand S valid range: T0~T183
Operand m valid range: K1~K32,767 (unit: 100 ms)
Operand D valid range: S912~S1023
3. Flag: M1048 (ON: Alarm is active), M1049 (ON: Alarm monitoring is enabled)
4. See ANR instruction for more information
Program Example:
If X3 = ON for more than 5 sec, alarm step relay S999 will be ON. S999 will remains ON after X3 is
reset. (T10 will be reset, present value = 0)
X3
ANS T10 K50 S999

Table of Contents