DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming
API
Mnemonic Operands Function
SS2
SX2
46 ANS
Timed Annunciator Set
Type
OP
Bit Devices Word devices Program Steps
X Y M S K H KnX
KnY
KnM
KnS
T C D E F
ANS: 7 steps
SS2
SX2
SS2
SX2
SS2
SX2
Operands:
S: Alarm timer m: Time setting D: Alarm
Explanations:
1. ANS instruction is used to drive the output alarm device in designated time.
2. Operand S valid range: T0~T183
Operand m valid range: K1~K32,767 (unit: 100 ms)
Operand D valid range: S912~S1023
3. Flag: M1048 (ON: Alarm is active), M1049 (ON: Alarm monitoring is enabled)
4. See ANR instruction for more information
Program Example:
If X3 = ON for more than 5 sec, alarm step relay S999 will be ON. S999 will remains ON after X3 is
reset. (T10 will be reset, present value = 0)