Page #304 background image
3. Instruction Set
3-183
4. M10~ M13 = ON when the current value of C10 falls between lower and upper bounds.
Lower-bound value
Upper- bound value
Current value of C10
Output
D100= 40
D101 = 100
40≦C10≦100
M10 = ON
D102 = 120
D103 = 210
120≦C10≦210
M11 = ON
D104 = 140
D105 = 170
140≦C10≦170
M12 = ON
D106 = 150
D107 = 390
150≦C10≦390
M13 = ON
5. If the lower bound value is bigger than upper bound value, when C10<60 or C10 > 140, M12 =
ON.
Lower- bound value
Upper- bound value
Current value of C10
Output
D100 = 40
D101 = 100
40≦C10≦100
M10 = ON
D102 = 120
D103 = 210
120≦C10≦210
M11 = ON
D104 = 140
D105 = 60
60≦C10≦140
M12 = OFF
D106 = 150
D107 = 390
150≦C10≦390
M13 = ON
4002000
40
100
120 210
60
140
15
0 390
M10
M11
M12
M13