P50 Agile P253
6 Protection Functions
P253/EN M/C
6-15
t =
T *
K
I
I
s
α
- 1
+ L
Where;
t: Operation time
K: Constant (see the table)
I: Measured current
Is: Current threshold setting
α: Constant (see the table)
L: ANSI/IEEE constant (zero for IEC curve)
T: Time multiplier setting (TMS) for IEC curves or Time dial setting (TD) for IEEE curves
Description Standard K α L
Define Time DT - - 0
Standard Inverse IEC 0.14 0.02 0
Standard Inverse(1.3sec) --- 0.06 0.02 0
Very Inverse IEC 13.5 1 0
Extremely inverse
IEC
80
2
0
Long Time Inverse
UK
120
1
0
Moderate Inverse IEEE 0.0515 0.02 0.114
Very Inverse IEEE 19.61 2 0.491
Extremely Inverse IEEE 28.2 2 0.1217
US Inverse CO8 5.95 2 0.18
US Short Time Inverse
CO2
0.02394
0.02
0.01694
2.4.2 Principle of Protection Function Implementation
An energising quantity is a current input from a system current transformer or another quantity derived
from the current input. The energising quantities are extracted from the power system and presented
to the IED in the form of analogue signals. These analogue signals are then converted to digital
quantities where they can be processed by the IEDs internal processor.
In general, an energising quantity is compared with a threshold value, which may be settable or hard-
coded depending on the function. If the quantity exceeds (for overvalues) or falls short of (for
undervalues) the threshold, a signal is produced, which when gated with the various inhibit and
blocking functions becomes the Start signal for that protection function. This Start signal is generally
made available to Fixed Scheme logic for further processing. It is also passed through a timer function
to produce the Trip signal. The timer function may be an IDMT curve, or a Definite Time delay,
depending on the function. The timer can be configured by a range of settings to define such
parameters as the type of curve, The Time Multiplier Setting, the IDMT constants and Definite Time
delay.
In P253 there are several independent stages for each of the functions. All the stages (1, 2 and 3) can
be set for DT/IDMT timer function. If the DT time delay is set to '0', then the function is known to be
"instantaneous". In many instances the term “instantaneous protection” is used loosely to describe
Definite Time protection stages even when the stage may not theoretically be instantaneous.