Password protected window for Limit NB Starts i.e. Hot Start Status
(Hot Start NB), Cold Start Stat (Cold Start NB),
T.Betw.St.Status (Time Betwn Start), Inhib. Strt Time
Note: Setting will be seen only when it is enabled in Configuration
setting.
2.3.16.2 Group 1 –System Configuration Submenu
2.3.16.2.1
Edit Settings
(if 2
nd
harmonic is disabled)
GROUP 1
Password protected window for “GROUP 1’’ setting:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Note: Group 1 settings will be seen only
Password protected window for System Configuration i.e. 2nd
Harmonic (Disabled/Enabled), 2nd Harmonic Threshold and I>lift 2H.
2nd Harmonic
Disabled
Editable setting
By using the (+ /5) or (- /6) key, 2nd Harmonic set as Disabled.
2.3.16.2.2
Edit Settings
(if 2
nd
harmonic is enabled)
GROUP 1
Password protected window for
setting:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Note: Group 1 settings will be seen only when it is enabled in
Configuration menu.
SYSTEM CONFIG
Password Protected window for System Configuration i.e. 2nd
Harmonic (Disabled/Enabled), 2nd Harmonic Threshold and I>lift 2H.
By using the (+ /5) or (- /6) key, 2nd Harmonic is Enabled.
2nd Harm Thresh
20%
Editable setting
By using the (+ /5) or (- /6) key, the desired 2nd Harmonic
Threshold can be set. The setting range is 5% to 70% in steps of 1%.