EasyManuals Logo
Home>GE>Relays>P50 Agile P253

GE P50 Agile P253 User Manual

GE P50 Agile P253
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #265 background imageLoading...
Page #265 background image
P50 Agile P253
11 Commissioning Instructions
P253/EN M/C
11-7
2.1.11.3 Performing the Test
1. Ensure the timer is reset.
2. Apply a current of twice the setting. This is shown in the I>1 Current Set cell in the
OVERCURRENT menu.
3. When the timer stops, make a note of the time displayed.
4. Check that the red trip LED has illuminated.
2.1.11.4 Checking the Operating Time
Check that the operating time recorded by the timer is within the range shown below.
For all characteristics, allowance must be made for the accuracy of the test equipment being used.
Characteristic
Operating time at twice current setting and time multiplier/
time dial setting of 1.0
Nominal (seconds) Range (seconds)
DT I>1 Time Delay setting Setting ±5% or 55ms whichever is greater
IEC S Inverse 10.03
Please refer to the Technical Specifications
chapter for operating time accuracy
IEC V Inverse 13.50
IEC E Inverse
26.67
UK LT Inverse 20.00
IEEE M Inverse 3.8
IEEE V Inverse 7.03
IEEE E Inverse 9.50
US Inverse
2.16
US ST Inverse
12.12
Note: With the exception of the definite time characteristic, the operating times given are for a Time
Multiplier Setting (TMS) or Time Dial Setting (TDS) of 1. For other values of TMS or TDS, the values
need to be modified accordingly.
Caution: When the tests are complete, restore all settings that were disabled.
2.1.12 Thermal Overload Protection
The P253 relay models the time-current thermal characteristic of a motor by internally generating a
thermal replica of the machine. The aim of this test is to check:
The presence of a thermal alarm as soon as the thermal state reaches the set threshold
The time to a thermal trip in case of a thermal overload
The measurements of the thermal load and thermal state
The settings of this function are listed in the THERMAL OVERLOAD, GROUP 1 menu column. Check
these settings before the test.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P50 Agile P253 and is the answer not in the manual?

GE P50 Agile P253 Specifications

General IconGeneral
BrandGE
ModelP50 Agile P253
CategoryRelays
LanguageEnglish

Related product manuals