By using the (+ /5) or (- /6) key, the desired I>1 Current Setting can
be set. The setting range is from 0.05 to 4 In in steps of 0.01 In.
I>1 TMS
1.000
Editable setting
By using the (+ /5) or (- /6) key, the desired I>1 TMS setting can be
done. The setting range is from 0.025 to 1.2 in steps of 0.005.
I>1 Reset Char
DT
Read-only setting
I>1 Reset Char function is fixed as DT (Definite Time).
By using the (+ /5) or (- /6) key, the desired I>1 tRESET setting can
be done. The setting range is from 0 to 100s in steps of 0.01s.
I>1 2H Blocking
Disabled
Editable setting
By using the (+ /5) or (- /6) key, I>12H Blocking function can be
Enabled / Disabled.
2.3.16.3.3
Edit Settings
(if I>1 Function is selected for IEEE / US curve)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Note: Group 1 setting will be seen only when it is enabled in
Configuration setting.
OVERCURRENT
Password protected window for
i.e. I>1 Function, I>2
Function and I>3 Function setting to Disabled / DT/ IEC S Inverse/
S Inverse (1.3Sec)/ IEC V Inverse/ IEC E Inverse/ UK LT Inverse /IEEE
M Inverse/ IEEE V Inverse/ IEEE E Inverse /US Inverse /US ST Inverse
I>1 Function
IEEE M Inverse
Editable setting
By using the (+ /5) or (- /6) key, I>1Function is set as
IEEE M Inverse.
By using the (+ /5) or (- /6) key, the desired I>1 Current Setting can
be set. The setting range is from 0.05 to 4 In in steps of 0.01 In.