EasyManuals Logo
Home>GE>Relays>P50 Agile P253

GE P50 Agile P253 User Manual

GE P50 Agile P253
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #68 background imageLoading...
Page #68 background image
5 Configuration
P50 Agile P253
5-28
P253/EN M/C
Measure’t setup
ABC
Editable setting
By using the (+ /5) or (- /6) key, Measurement Setup can be set as
ABC / RYB.
Setting Values
Secondary
Editable setting
By using the (+ /5) or (- /6) key, Setting Values can be set as Primary
/ Secondary.
2.3.9 Transformer Ratios Menu
2.3.9.1 View / Edit Settings
TRANS. RATIOS
Password protected window for “TRANS. RATIOS settings:
Phase CT Primary, Phase CT Secondary, E/F CT Primary and E/F CT
Secondary.
Phase CT Primary
100 A
Editable setting
By using the (+ /5) or (- /6) key, Phase CT Primary can be set. The
setting range is from 1A to 30000A in steps of 1A.
Phase CT Sec’y
1 A
Editable setting
By using the (+ /5) or (- /6) key, Phase CT Secondary can be set as
1A / 5A.
E/F CT Primary
100 A
Editable setting
By using the (+ /5) or (- /6) key, E/F CT Primary can be set. The
setting range is from 1A to 30000A in steps of 1A.
E/F CT Secondary
1 A
Editable setting
By using the (+ /5) or (- /6) key, E/F CT Secondary can be set as 1A /
5A.
2.3.10 Record Control Menu
2.3.10.1 View / Edit Settings
RECORD CONTROL
Password protected window for
“RECORD CONTROL’’
settings:
Clear Events (Yes/No), Clear Faults (Yes/No)
, Clear Dist Recs
(Yes/No), Clear Maint (Yes/No), Thermal Reset (Yes/No), Reset Nb Em
Rst (Yes/No), Reset Nb of St (Yes/No), Reset Motor RunT (Yes/No) and
Reset CB Data (Yes/No).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P50 Agile P253 and is the answer not in the manual?

GE P50 Agile P253 Specifications

General IconGeneral
BrandGE
ModelP50 Agile P253
CategoryRelays
LanguageEnglish

Related product manuals