By using the (+ /5) or (- /6) key, the desired I>1 Time Dial can be set.
The setting range is from 0.01 to 100 in steps of 0.01.
I>1 Reset Char
DT
Editable setting
By using the (+ /5) or (- /6) key, I>1 Reset Char function can be set
as IDMT / DT.
I>1 tRESET
0.01 S
Editable setting
By using the (+ /5) or (- /6) key, I>1 tRESET can be set. The setting
range is from 0 to 100s in steps of 0.01s.
By using the (+ /5) or (- /6) key, I>1 RTMS can be set. The setting
range is from 0.025 to 1.2 in steps of 0.005
I>1 2H Blocking
Disabled
Editable setting
By using the (+ /5) or (- /6) key, I>12H Blocking function can be
Enabled / Disabled.
2.3.16.3.4
Edit Settings
(if I>1 Function is selected for DT)
GROUP 1
Password protected window for “GROUP 1’’ settings:
SYSTEM CONFIG, OVERCURRENT, NEG SEQUENCE O/C, EARTH
FAULT 1, EARTH FAULT 2, THERMAL OVERLOAD, LOSS OF LOAD,
CB FAIL, STALL DETECTION and LIMITS NB STARTS.
Note: Group 1 setting will be seen only when it is enabled in
Configuration setting.
OVERCURRENT
Password protected window for
i.e. I>1 Function, I>2
Function and I>3 Function setting to Disabled / DT/ IEC S Inverse/ S
Inverse (1.3Sec)/ IEC V Inverse/ IEC E Inverse/ UK LT Inverse /IEEE M
Inverse/ IEEE V Inverse/ IEEE E Inverse /US Inverse /US ST Inverse
I>1 Function
DT
Editable setting
By using the (+ /5) or (- /6) key, I>1Function is set as DT.
By using the (+ /5) or (- /6) key, I>1 Current Setting can be set. The
setting range is from 0.05 to 35 In in steps of 0.01 In.
Note: For I>3 Function, the setting range is from 1 to 35 In in steps of
0.01 In.