4. CONFIGURATION
4.11.1. CODE - Identification code
Acronym Scrolling message Submenu Attributes
CODE INSTRUMENT ID CODE FOR SERIAL COMM SERIA R W
The parameter shows and sets the identifying address of the indicator in a Modbus serial network. Generally should not
be set to “1”
Unit of measurement: Number
Options: 1...247
4.11.2. KBAUD - Selecting communication speed
Acronym Scrolling message Submenu Attributes
KBAUD COMMUNICATION SPEED SERIA R W
The parameter shows and sets the communication speed for the serial port.
Unit of measurement: kbaud
Options: 1.2 = 1200 baud
2.4 = 2400 baud
4.8 = 4800 baud
9.6 = 9600 baud
19.2 = 19200 baud
38.4 = 38400 baud
57.6 = 57600 baud
115.2 = 115200 baud
4.11.3. PAr - Selecting parity
Acronym Scrolling message Submenu Attributes
PAr PARITY SERIA R W
The parameter shows and sets the parity used in serial communication.
Unit of measurement: -
Options: NONE = No parity
ODD = Odd parity
EVEN = Even parity