Control and operation
Initial starting after out of service period
4.5 Initial starting after out of service period
4.5.1 Preparation of initial starting
For initial starting or after a suspension of activity, perform the following tasks:
u Replace engine oil. Refer to chapter Maintenance.
u Replace oil filters. Refer to chapter Maintenance.
u Perform a general visual inspection. Refer to chapter Maintenance.
u Check coolant level. Refer to chapter Maintenance.
u Drain off water and sediment of fuel tank. Refer to Operation and Maintenance Manual.
u Check water separator of fuel pre-filter and bleed water if necessary. Refer to Operation and
Maintenance Manual.
u Check visually the starter, battery charging alternator.
u Check belt, and replace if necessary. Refer to chapter Maintenance.
u Vent the fuel system. Refer to Operation and Maintenance Manual of generator set.