EasyManuals Logo
Home>Lennox>Control Systems>Harmony III

Lennox Harmony III Installation Instructions

Lennox Harmony III
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
GENERAL
Page 9
HARMONY IIIT ZONE CONTROL SYSTEM
Zone Control Panel Jumpers (Determining PIAB Jumper Settings)
Determining PIAB Jumper Settings
NOTE − Use the PIAB Calculation Worksheet on Page 60
(also see example below) to help calculate the zone con-
trol system PIAB settings.
1. From a cooling load analysis, determine what CFM is
required for each zone. Also, from the air handler, de-
termine its minimum and maximum CFM ratings.
2. Using the PIAB formula, found in Table 5 and re-
flected in the worksheet below, calculate the Percent
Into Adjustment Band (PIAB) using the values from
step 1 for each zone. Table 5 also gives example CFM
values to illustrates how to determine the correct
jumper for the PIAB for Zone 1 using those values.
3. Set the air selection jumper for the zone using the per-
cent air determined in step 2. If the percent air falls be-
tween available jumper settings, select the nearest
unit of ten.
4. For each zone, repeat steps 1 through 3.
Note − See page 8 for information on 140F DAS (dis-
charge air sensor) jumper used on Zone 1 PIAB.
Table 5. Determine PIAB jumper setting
example CFM values
Required CFM CFM
Zone 1 Zone 2 Zone 3 Zone 4 Min. Max.
1020 1500 720 OFF 720 2200*
*High cool jumper setting
PIAB formula
100
(Req’d CFM min. CFM)
(Max. CFM min. CFM)
x
Using example values above, find PIAB for Zone 1:
PIAB (1020 − 720) = 300 =.20. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(2220 − 720) =1500. . . . . . . . . . . . . . . . . . . . . . .
PIAB Jumper setting % .20 x 100 20%. . . . . . . . . . . . . . . . . . . .
SETUP TIP!
PIAB calculations should provide a good starting point for
setting jumpers. It may also be beneficial to set jumpers at
a higher percentage of airflow such that the sound of air
rushing is objectionable, and then reduce it incrementally
by 10% until: 1) the sound of air rushing is not objection-
able, and 2) ample, but not excessive, air volume is being
provided to adequately heat or cool the zone.
PIAB Calculation Example (see worksheet on Page 60 )
PIAB = [(Required CFM − Minimum CFM) / (Maximum CFM − Minimum CFM)] * 100
Sample CFM ' Required Minimum Maximum Minimum
Sample PIAB = ([___920 450 ] / [ 2000 450 ]) x 100
==
bb
Sample PIAB = ([ 470 ] / [ 1550 ]) x 100
=
b
Sample PIAB = [ 0.303 ] x 100 = 30 %
Zone Control Panel Jumpers (Air Reduction)
Continuous Air Reduction Jumpers
During continuous fan mode without either a heating or
cooling demand, the blower runs at the total percentage of
the CFM jumper settings of the zones calling for continu-
ous fan (not to exceed 100% of blower capacity). A contin-
uous air reduction jumper allows the blower speed to be re-
duced by a percentage during continuous fan mode.
The selections are 75%, 50%, 25% and 0%. At the factory,
the jumper is set on 0%. Set the jumper to the position
equal to the amount of continuous air reduction desired.
See figure 9.
NOTE − If the calculations using a reduction percentage
indicated a resulting CFM lower than the blower’s mini-
mum CFM rating, the blower will deliver its minimum CFM
(see figure 6 on Page 8).
Heating Air Reduction Jumpers
NOTE − For heat pump applications, ALWAYS set the
jumper on 0%. High head pressures may result if air is re-
duced during heating mode.
NOTE − For use in warm−climate areas where units have
high cooling capacity with low heat capacity, ALWAYS set
the jumper on 0%.
The heating air reduction jumper enables the blower
speed, during heating only, to run at a reduced rate
compared to the cooling blower speed.
The selections are 40%, 20% and 0%. Jumpers are set to
0% from the factory. Set the jumper to the position equal to
the amount of heating air reduction desired. See figure 9.
CONTINUOUS HEATING
0%
20%
40%
75%
50%
0%
25%
factory
settings
shown
heating jumper
Must be set on 0%
for heat pump
application
Figure 9. Air Reduction Jumper Settings

Table of Contents

Other manuals for Lennox Harmony III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Harmony III and is the answer not in the manual?

Lennox Harmony III Specifications

General IconGeneral
BrandLennox
ModelHarmony III
CategoryControl Systems
LanguageEnglish

Related product manuals