3.5 How to congure parameters
3.5.1 Parameter clear/All parameter clear
Parameter settings may have been changed if the inverter is used.
Use this procedure to restore parameters to their initial values.
Setting Description
0 Not executed.
1
Set parameters back to the initial values. (Parameter clear sets back all parameters except calibration
parameters, terminal function selection parameters to the initial values.) Refer to the parameter list for
information on the availability of clear parameter and clear all parameters functions for each parameter.
Operation Display
1
Screen at power-ON
The monitor display appears.
2
Changing the operation mode
Press to choose the PU operation mode.
PU indication is lit.
3
Parameter setting mode
Press to choose the parameter setting
mode.
PRM indication is lit.
(The parameter number read previously appears.)
4
Selecting the parameter number
Turn until ( ) appears
Parameter clear
All parameter clear
5
Reading settings
Press to read the present setting.
"
"(initial value) appears.
6
Changing the setting
Turn to change it to the set value " ".
7
Parameter settings
Press to nalize the setting.
"1" and "Pr.CL"/"ALLC" ashes.
Parameter clear
All parameter clear
Check the values of several parameter settings when the clear all parameters function cannot be performed.
Pr. 77 "0", Pr. 79 "0", Pr. 340 "10", and Pr. 551 "9999"
POINT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FREQROL-E700 and is the answer not in the manual?

Mitsubishi FREQROL-E700 Specifications

General IconGeneral
BrandMitsubishi
ModelFREQROL-E700
CategoryInverter
LanguageEnglish

Related product manuals