Control Units
FP0
2-12
Matsushita Automation Controls
2.2 Specifications
Item
Relay output type
Transistor output
type
It
em
C10RS/C10CRS
C10RM/C10CRM
C14RS/C14CRS
C14RM/C14CRM
C16T/C16CT
C16P/C16CP
C32T/C32CT
C32P/C32CP
Special
f
t
i
Pulse catch input
Total 6 points
X0
and
X1:
50
μ
s
functions
Interrupt input
X0 and X1: 50
μ
s
X2 to X5: 100
μ
s
RS232C port (
*
Note 1)
Available unit: FP0-C10CRS, C10CRM, C14CRS,
C14CRM, C16CT, C16CP, C32CT and
C32CP
Baud rate: 300, 600, 1200, 2400. 4800, 9600, and
19200 bps
Transmission distance: 3m/9.84 ft.
Terminal block: 3-pin, made by Phoenix Contact Co.
(product number: MKDS 1/3-3.5)
Communication method: half-duplex
Periodic al interrupt
0.5 ms to 30 s interval
Constant scan
Available
High-speed counter
function
(
*
Note 2, 3)
Counter mode: Addition/subtraction (one phase)
- Input point number: 4 channels maximum
- Maximum counting speed: 10 kHz maximum for
all 4 channels (
*
Note 4)
- Input contacts used:
- Minimum input pulse width: X0, X1.. 50
μ
s <10 kHz>
X3, X4 ..100
μ
s <5 kHz>
X0: count input (ch 0)
X1: count input (ch 1)
X2: reset input (
*
Note 5)
X3: count input (ch 2)
X4: count input (ch 3)
X5: reset input (
*
Note 5)
Counter mode: Two-phase/individual/direction decision
(two phase)
- Input point number: 2 channels maximum
- Maximum counting speed: 2 kHz maximum for all 2
channels
- Input contacts used:
- Minimum input pulse width: X0, X1.. 50
μ
s <10 kHz>
X3, X4 ..100
μ
s <5 kHz>
X0: count input (ch 0)
X1: count input (ch 0)
X2: reset input
X3: count input (ch 2)
X4: count input (ch 2)
X5: reset input
Pulse
output
function
Output point
number
——————
Two independent points
(Y0 and Y1)
(No interpolation function)
f
u
n
c
t
i
o
n
(
*
Note
3)
Output
frequency
——————
40 Hz to 10 kHz
(Y0/Y1: one-point output)
40 Hz to 5 kHz
(Y0/Y1: two-point output)
.
next page

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NAiS FP0-C32T and is the answer not in the manual?

NAiS FP0-C32T Specifications

General IconGeneral
BrandNAiS
ModelFP0-C32T
CategoryController
LanguageEnglish

Related product manuals