I/O Allocation
FP0
5-5
Matsushita Automation Controls
5.3 Expansion I/O Unit
5.3 Expansion I/O Unit
Up to three expansion I/O units can be added.
I/O numbers do not need to be set as I/O allocation is performed automatically by the
FP0 control unit when an expansion I/O unit is added.
The I/O allocation of expansion I/O unit is determined by the installation location.
I/O number
Type
First
expansion
Second
expansion
Third
expansion
E8RS/E8RM Input: 4 points
X20 to X23 X40 to X43 X60 to X63
Output: 4 points
Y20 to Y23 Y40 to Y43 Y60 to Y63
E8X Input: 8 points
X20 to X27 X40 to X47 X60 to X67
E8YT/E8YP Output: 8 points
Y20 to Y27 Y40 to Y47 Y60 to Y67
E16RS/E16RM/
Input: 8 points
X20 to X27 X40 to X47 X60 to X67
E16T/E16P
Output: 8 points
Y20 to Y27 Y40 to Y47 Y60 to Y67
E16X Input: 16 points
X20 to X2F X40 to X4F X60 to X6F
E16YT/E16YP Output: 16 points
Y20 to Y2F Y40 to Y4F Y60 to Y6F
E32T/E32P Input: 16 points
X20 to X2F X40 to X4F X60 to X6F
Output: 16 points
Y20 to Y2F Y40 to Y4F Y60 to Y6F
Third expansion
Second expansion
First expansion
Control unit