Control Units
FP0
2-16
Matsushita Automation Controls
2.2 Specifications
2.2.4 Output Specifications
2.2.4.1 Relay Output Type
FP0 relay output types: C10RM, C10CRM, C10RS, C10CRS, C14RM, C14CRM,
C14RS, C14CRS
Item Description
Output type
Normally open (1 Form A) relay output
Rated control capacity
2 A 250 V AC, 2 A 30 V DC (4.5 A maximum per common)
Output points
per common
C10RM,
C10CRM,
C10RS,
C10CRS
2 points/common
+
1 point/common +1 point/common
C14RM,
C14CRM,
C14RS,
C14CRS
4 points/common + 1 point/common + 1 point/common
Response time OFF
o
ON
approx. 10 ms
ON
o
OFF
approx. 8 ms
Mechanical life time
20,000,000 operations or more
Electrical life time
100,000 operations or more
Surge absorber
None
Operating mode indicator