Page 2 AFP-2800 - Fire Indicator Panel – Emergency Operators Guide
© N
OTIFIER
I
NERTIA
P
TY
L
TD
, 2001
WWW
.
INERTIA
.
COM
.
AU
SECTION 1:
SECTION 1:SECTION 1:
SECTION 1:
E
MERGENCY
O
PERATORS
G
UIDE
Isolate Bells
Press: EXT BELL ISOLATE
• EXT BELL ISOLATE LED will light
• The Bells & Buzzer will stop
• A subsequent alarm will restart the Buzzer but not the bells
• The bell isolate can be toggled by pressing the button a second time
Isolate Warning System
Press: WARN SYS ISOLATE
• WARN SYS ISOLATE LED will light
• The warning system will stop
• A subsequent alarm will restart the Buzzer but not the warning
system
• The warning system isolate can by toggled by pressing the button a
second time
Acknowledging an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: ACK to acknowledge
• This will individually acknowledge alarms
• Once all alarms are acknowledged the alarm LED will go steady
Resetting an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: RESET then press ACK to confirm the resetting
• This will individually reset alarms
• Resets zone in alarm and clears all alarm outputs
• If alarm is still present, the zone(s) will re-alarm again after about 5
seconds
Isolate an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: ISOL then press ACK to confirm the isolation
Isolates the point in alarm and clears it’s alarm outputs
Isolating a zone automatically acknowledges the zone