33 AFP-3030 Operations Manual — P/N DOC-01-039:A 26/11/2015
Operation of the Control Panel Mass Notification Fault Event
Flashes the SYSTEM FAULT LED on the fire panel and any annunciator points programmed for
general fault
Displays a Type Code that indicates the type of device with a fault
Displays FAULT in the upper left corner of the panel display the type of fault and information
specific to the device.
Sends a Fault message to the history buffer, installed printer and annunciators
Activates special zone ZF22
Activates the Fault relay and any devices programmed as General Fault and General Pending
Does not cause any devices programmed as “Resound on Fault” to resound
Sends a Fault message to the proprietary receiver via the network, if applicable
When an unacknowledged event with a higher priority exists, the control panel retains the
indications of the higher priority event (the message, lit LED, audible tone, etc.) illuminating the
SYSTEM FAULT LED, and sending a Fault message to the history buffer, installed printer and
annunciators.
Figure 2.11 Sample Message for MN Fault
2.10.2 How to Respond to a Mass Notification Fault
If the control panel indicates a fault, the operator can do the following:
1. Press the SILENCE BUZZER
key to silence the panel sounder.
The control panel sends an acknowledge message to the History buffer, installed printers and
annunciators.
2. Check the fault message for an indication of the fault.
Press the MORE INFO soft key to display the MORE INFORMATION screen and view
additional information on the device and possibly preprogrammed text for recommended
action. (Refer to Figure 1.9 on page 11 for an example of the this screen and an explanation of
its fields.)
3. Correct the condition causing the fault. If the fault clears, the control panel sends a Clear Fault
message to the History buffer, installed printers and annunciators.
If all faults clear and no supervisory signals or fire alarms exist, the control panel does the follow-
ing:
Returns to Normal operation (indicated by the “System Normal” message)
Sends a “System Normal” message to the panel display, History buffer, installed printers and
annunciators
Restores faults automatically - even if faults are not acknowledged
OTHER: 2 OF 2
ACKNOWLEDGED MN FAULT
SECURITY OFFICE MAIN BLDG
Monitor L01M134 ZF21 ECS/MN TMON
10:35:17A TUE 02 DEC 2014 L01D134
MORE INFO...
1 OTH L02D003
Detector L02D003
2 OTH L01M134
Monitor L01M134
ALM:0 SUP:0 FLT:0 DIS:0 OTHER:2
11:58:43A TUE 02, DEC, 2014

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals