Appendix B Canadian Applications Standalone Application
64 NFS-3030 Installation PN 51330:C 10/28/2003
Appendix B Canadian Applications
B.1 Standalone Application
CPU-3030D, with its integral keypad/display, meets Canadian requirements for standalone applications.
Its 640-character, multi-line display complies with ULC requirements for primary displays.
B.2 Local Network Application
To meet ULC requirements, the network’s Manual Controls may only be operated from one location at
any given time.
When panels are networked (using NCM Network Control Modules), employ AKS-1 Key Switch on
each panel’s Primary Annunciator to enable its functions. NCA may be a Primary Annunciator when
AKS-1 is installed. Refer to the NCA Manual (P/N 51482) for more information.
Note: Only one key should be issued for a networked system.
An NCA or Network Control Station (NCS) may be employed as a Display and Control Center. In the
event that communication fails between the panels and the Control Center, the panels will continue to
function in local/standalone mode.
B.3 Automatic Alarm Signal Silence
If selecting this feature for a system requiring annunciators, consult the Authority Having Jurisdiction.
B.4 Annunciator Applications
1. In Canada, the ACM series annunciator modules must be used to annunciate the fire alarm input
points/zones only, if no multi-line sequential display is installed.
2. For Canadian applications, the following LED colors must be employed:
• Red must be used to indicate active alarm inputs.
• Yellow must be used to indicate supervisory, burglary or trouble signals.
• Green must be used to indicate the presence of power or an activated output.
B.5 Releasing Devices
Supervision for shorts is required; use REL-47K and type code REL CKT ULC.
Refer to Section 4.6 “Releasing Applications”.