A Appendices
A - 30
E5@C-T Digital Temperature Controllers User’s Manual (H185)
Direct Setting of
Position Proportional
MV
pmvd OFF, ON off, on OFF None
PV Rate of Change
Calculation Period
pvrp 1 to 999 20 Sampling
period
Heating/Cooling Tuning
Method
hctm 0: Same as heating control
1: Linear
2: Air cooling
3: Water cooling
0None
Minimum Output
ON/OFF Band
ompw 0.0 to 50.0 1.0 %
LCT Cooling Output
Min. ON Time
lcmt 0.1 to 1.0 0.2 Seconds
PF Setting pf OFF: OFF
RUN: RUN
RST: Reset
R-R: Run/reset
HOLD: Hold/clear hold
ADV: Advance
AT-2: 100% AT execute/cancel
AT-1: 40% AT execute/cancel
ATA2: All PID 100% AT execute/cancel
ATA1: All PID 40% AT execute/cancel
LAT: Alarm Latch Cancel
A-M: Auto/manual
PFDP: Monitor/setting item
SHFT: Digit Shift Key
off
run
rst
r-r
hold
adv
at-2
at-1
ata2
ata1
lat
a-m
pfdp
shft
SHFT None
PF Monotor/Setting
Item 1
pfd1 0: Disabled
1: PV/SP/Multi-SP/Program No. monitor and
segment No. monitor
2: PV/SP/MV (heating) (valve opening for
Position-proportional Models)
3: PV/SP/MV monitor (cooling)
4: PV/SP/Remaining segment time
5: Program Number
6: Segment No. monitor
7: Remaining standby time monitor
8: Elapsed program time monitor
9: Remaining program time monitor
10: Elapsed segment time monitor
11: Remaining segment time monitor
12: Program execution repetitions monitor
13: Proportional band
14: Integral time
15: Derivative time
16: Proportional band (cooling)
17: Integral time (cooling)
18: Derivative time (cooling)
19: Alarm value 1
20: Alarm value upper limit 1
21: Alarm value lower limit 1
22: Alarm value 2
23: Alarm value upper limit 2
24: Alarm value lower limit 2
25: Alarm value 3
26: Alarm value upper limit 3
27: Alarm value lower limit 3
28: Alarm value 4
29: Alarm value upper limit 4
30: Alarm value lower limit 4
1None
PF Monitor/Setting
Item 2
pfd2 Same as Monitor/Setting Item 1. 0 None
PF Monitor/Setting
Item 3
pfd3 Same as Monitor/Setting Item 1. 0 None
PF Monitor/Setting
Item 4
pfd4 Same as Monitor/Setting Item 1. 0 None
PF Monitor/Setting
Item 5
pfd5 Same as Monitor/Setting Item 1. 0 None
Parameters Characters Setting (monitor) value Display Default Unit