E5@C-T Digital Temperature Controllers User’s Manual (H185)
A-6 Parameter Operation Lists
A
A-6-8 Advanced Function Setting Level
Auxiliary Output 1
Assignment
sub1 NONE: No assignment none ALM1
*Controllers
without HB
and HS
alarm
detection:
HA
None
O: Control output (heating) o
C-O: Control output (cooling) c-o
ALM1: Alarm 1 alm1
ALM2: Alarm 2 alm2
ALM3: Alarm 3 alm3
ALM4: Alarm 4 alm4
HA: Heater alarm (HB + HS) ha
HB: Heater burnout alarm (HB) hb
HS: Heater short alarm (HS) hs
S.ERR: Input error s.err
P.END: Program end output p.end
STG: Stage output stg
RUN: RUN output run
TS1: Time signal 1 output ts1
TS2: Time signal 2 output ts2
ALM: Integrated alarm alm
WR1: Work bit 1
*3
wr1
WR2: Work bit 2
*3
wr2
WR3: Work bit 3
*3
wr3
WR4: Work bit 4
*3
wr4
WR5: Work bit 5
*3
wr5
WR6: Work bit 6
*3
wr6
WR7: Work bit 7
*3
wr7
WR8: Work bit 8
*3
wr8
Auxiliary Output 2
Assignment
sub2 Same as the Auxiliary Output 1 Assignment
parameter.
Same as the
Auxiliary
Output 1
Assignment
parameter.
ALM2 None
Auxiliary Output 3
Assignment
sub3 Same as the Auxiliary Output 1 Assignment
parameter.
Same as the
Auxiliary
Output 1
Assignment
parameter.
ALM3 None
Auxiliary Output 4
Assignment
sub4 Same as the Auxiliary Output 1 Assignment
parameter.
Same as the
Auxiliary
Output 1
Assignment
parameter.
ALM4 None
Integrated Alarm
Assignment
alma 0 to 255
Alarm 1: +1
Alarm 2: +2
Alarm 3: +4
Alarm 4: +8
HB alarm: +16
HS alarm: +32
Input error: +64
Not used: +128
49 None
Alarm SP Selection alsp SP-M: Present SP
TSP: Segment SP
sp-m, tsp SP-M None
SP Tracking sptr OFF, ON off, on OFF None
PID Set Automatic
Selection Data
pidi PV, deviation, or SP pv, dv, sp PV None
PID Set Automatic
Selection Hysteresis
pidh 0.10 to 99.99 0.50 %FS
PV Dead Band p-db 0 to 9999 0 EU
Manual MV Limit
Enable
manl OFF, ON off, on OFF None