6 - 25
6 Installation
NX-series EtherNet/IP Coupler Unit Users Manual (W536)
6-2 Control Panel Installation
6
6-2-1 Temperature
Forced Ventilation by Fan at Top of Panel
Forced Air Circulation by Fan in Closed Panel
Room Cooling (Cooling the Entire Room Where the Control Panel Is Located)
The EtherNet/IP Slave Terminal may not start normally if the temperature is below 0°C when the power
is turned ON.
Maintain an air temperature of at least approximately 5°C inside the panel, by implementing measures
such as installing a low-capacity space heater in the panel.
Alternatively, leave the EtherNet/IP Slave Terminal power ON to keep the EtherNet/IP Slave Terminal
warm.
Low Temperatures
Air filter
Fan
Forced Ventilation Method
EtherNet/IP
Slave
Terminal
EtherNet/IP
Slave
Terminal
Fan
Forced Circulation Method
EtherNet/IP
Slave
Terminal
EtherNet/IP
Slave
Terminal
Room Cooling
Air conditioner
Control panel