A - 27
Appendices
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
A-1 Supported CIP Objects
A
A-1-6 Clear Error Explicit Message Example Using CMND(490)
With an EtherNet/IP Unit, a CMND(490) instruction in the PLC CPU Unit’s ladder diagram program can
send explicit messages to a Slave Terminal.
The clear error service code (0x32 hex) is sent to the Slave Terminal at IP address 192.168.250.1,
using the CIP UCMM MESSAGE SEND command, 2810. The network number assigned to the Ether-
Net/IP network is 1. The IP address and node number of the EtherNet/IP Unit is 33.
The command data is stored in the DM Area starting at DM01000, and the response data is stored in
the DM Area starting at D02000. If the command ends with an error, the end code is stored in D00006
and command transmission is retried.
A-1-6 Clear Error Explicit Message Example Using CMND(490)
CPU Unit
CMND
(490)
Explicit
message
FINS
header
Note: Use 2810 for the
FINS command code.
FINS
header
Response
EtherNet/IP Unit
FINS
header
FINS
header
Explicit
message
Response
EtherNet/IP
network
Slave Terminal

Table of Contents

Other manuals for Omron NX-EIC202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX-EIC202 and is the answer not in the manual?

Omron NX-EIC202 Specifications

General IconGeneral
BrandOmron
ModelNX-EIC202
CategoryController
LanguageEnglish

Related product manuals