Appendices
A - 26
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
The instance attribute IDs are given in the following table.
Values of Capability Bits
Attribute IDs
Attribute ID
(hex)
Parameter name Description Attribute Data type Value (hex)
01 Interface Speed Interface communi-
cations speed
Read UDINT 00000064 (fixed)
02 Interface Flags Interface status Read DWORD 0000000F (fixed)
03 Physical Address Interface MAC
address
Read ARRAY OF
USINT
*1
*1. The array size is 6.
MAC address
0B Interface Capability Interface communi-
cations perfor-
mance
Read STRUCT ---
Capability Bits Communications
performance set-
ting
DWORD See below.
Speed/Duplex
Options
Communications
speed/bidirectional
options
STRUCT ---
Speed/Duplex
Array Count
Communications
speed/bidirectional
array size
USINT 01
Speed/Duplex
Array
Communications
speed/bidirectional
array
ARRAY
OF
STRUCT
---
Interface Speed Interface communi-
cations speed
UINT 0064 (fixed)
Interface
Duplex Mode
Interface bidirec-
tional mode
USINT 01: Full duplex
(fixed)
Bit Name Value
0 Manual Setting Requirement Reset Always FALSE.
1 Auto-negotiate Always TRUE.
2 Auto-MDIX Always TRUE.
3 Manual Speed/Duplex Always FALSE.
4 to 31 Reserved Always FALSE.

Table of Contents

Other manuals for Omron NX-EIC202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX-EIC202 and is the answer not in the manual?

Omron NX-EIC202 Specifications

General IconGeneral
BrandOmron
ModelNX-EIC202
CategoryController
LanguageEnglish

Related product manuals