Appendices
A - 4
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
The instance attribute IDs are given in the following table.
Value of Product Code
Values of Revision
Values of Status
Attribute IDs
Attribute ID
(hex)
Parameter name Description Attribute Data type Value (hex)
01 Vender ID Vendor ID Read UINT 002F (fixed)
02 Device Type Device type Read UINT 000C (fixed)
03 Product Code Product code Read UINT See below.
04 Revision Device CIP revision Read STRUCT See below.
Major Revision Major revision Read USINT
Minor Revision Minor revision Read USINT
05 Status EtherNet/IP Coupler Unit
status
Read WORD See below.
06 Serial Number Serial number Read UDINT
9D461D01
*1
*1. The value of Serial Number is different for each Unit.
07 Product Name Product name Read SHORT
STRING
094E582D45
4943323032
(fixed)
*2
*2. This indicates “NX-EIC202”.
Model Value of Product Code (hex)
NX-EIC202 067C (fixed)
Unit version of NX-EIC202
Value of Major Revision
(hex)
Value of Minor Revision
(hex)
Ver.1.0 01 02
Ver.1.2 01 03
Bit Name Description
0 Owned Indicates that the EtherNet/IP Coupler Unit opened a connection as the target
of a tag data link.
TRUE: Open.
FALSE: Not open.
1 Reserved Always FALSE.
2 Configured Indicates that the NX Unit configuration information has been confirmed.
TRUE: Confirmed.
FALSE: Not confirmed.
3 Reserved Always FALSE.
4-7 Extended Device
Status
Gives the status of the EtherNet/IP Coupler Unit.
02 hex: A timeout occurred in one or more target connections.
03 hex: A tag data link is not set.
05 hex: There is a Major Fault.
06 hex: One or more connections are communicating normally.