9-2 Diagnostics
Clear Fault You can clear a fault using any of several methods:
Program the SMC-Flex controller for a Clear Fault, which can be
found in Main Menu/Diagnostics/Faults.
If a human interface module is connected to the controller, press
the Stop button.
Note: A stop signal from HIM will always stop the motor and clear
the fault regardless of Logic Mask.
Cycle control power to the SMC-Flex controller.
Important: An overload fault cannot be reset until the Motor
Thermal Usage, parameter 12, value is below 75%. See
Protection and Diagnostics on page 1-11 for further
details.
Fault Buffer The SMC-Flex controller stores in memory the five most recent
faults. Display the fault buffer by selecting the View Faults Queue
and scrolling through the fault buffer parameters. The information is
stored as fault codes and fault descriptions. A fault code cross-
reference is provided in Table 9.A.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley SMC-Flex 150 and is the answer not in the manual?

Rockwell Automation Allen-Bradley SMC-Flex 150 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley SMC-Flex 150
CategoryController
LanguageEnglish

Related product manuals