Programming 4-11
Full Voltage Start The SMC-Flex controller may be programmed to provide a full
voltage start (output voltage to the motor reaches full voltage within
1/4 second) with the following programming:
Linear Speed The SMC-Flex provides the user the ability to control the motor speed
during starting and stopping maneuvers. A tach input is required as
specified in Linear Speed Acceleration on page 1-6
.
Parameter Option
Starting Mode
This must be programmed for Full Voltage.
Full Voltage
Parameter Option
Starting Mode
This must be programmed for Linear Speed.
Linear Speed
Ramp Time
This programs the time period that the controller will
ramp from 0 speed to full speed.
0…30 s
Kickstart Time
A boost of current is provided to the motor for the
programmed time period.
0.0…2.2 s
Kickstart Level
Adjusts the amount of current applied to the motor
during the kickstart time.
0…90% locked rotor
torque

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley SMC-Flex 150 and is the answer not in the manual?

Rockwell Automation Allen-Bradley SMC-Flex 150 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley SMC-Flex 150
CategoryController
LanguageEnglish

Related product manuals