1-18 Product Overview
Overtemperature
The SMC-Flex controller monitors the temperature of the SCRs and
Bypass by using internal thermistors. When the power poles’
maximum rated temperature is reached, the unit will shut down and
restart is inhibited.
An overtemperature condition can indicate inadequate ventilation,
high ambient temperature, overloading, or excessive cycling. After
the temperature is reduced to allowable levels, the fault can be
cleared.
Open Gate
An open gate fault indicates that improper SCR firing, typically
caused by an open SCR gate, has been detected on one of the power
poles. Before the controller shuts down, it will attempt to start the
motor a total of three times.
Line Faults
The SMC-Flex controller continually monitors line conditions for
abnormal factors. Pre-start protection includes:
Line Fault (with phase indication)
Line voltage loss
Missing load connection
–Shorted SCR
Running protection includes:
Line Fault (no phase indication)
Line voltage loss
Missing load connection
Phase Reversal
protection can be toggled either On or Off.
Phase Reversal protection is functional only at pre-start.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley SMC-Flex 150 and is the answer not in the manual?

Rockwell Automation Allen-Bradley SMC-Flex 150 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley SMC-Flex 150
CategoryController
LanguageEnglish

Related product manuals