1-18 Product Overview
Overtemperature
The SMC-Flex controller monitors the temperature of the SCRs and
Bypass by using internal thermistors. When the power poles’
maximum rated temperature is reached, the unit will shut down and
restart is inhibited.
An overtemperature condition can indicate inadequate ventilation,
high ambient temperature, overloading, or excessive cycling. After
the temperature is reduced to allowable levels, the fault can be
cleared.
Open Gate
An open gate fault indicates that improper SCR firing, typically
caused by an open SCR gate, has been detected on one of the power
poles. Before the controller shuts down, it will attempt to start the
motor a total of three times.
Line Faults
The SMC-Flex controller continually monitors line conditions for
abnormal factors. Pre-start protection includes:
• Line Fault (with phase indication)
– Line voltage loss
– Missing load connection
–Shorted SCR
Running protection includes:
• Line Fault (no phase indication)
– Line voltage loss
– Missing load connection
Phase Reversal
➀
protection can be toggled either On or Off.
➀ Phase Reversal protection is functional only at pre-start.