QSHT 5700 Inverter Safe Torque-off Function
Hardwired Safe Torque-off
276 MagneMotion
Rockwell Automation Publication MMI-UM007F-EN-P - September 2020
Safe Torque-off Wiring Requirements
The safe torque-off (STO) connector uses spring tension to secure the wire. Depress the num-
bered tab along side each pin to insert or release each wire. Two rows of pins are provided for
inverter-to-inverter connections. Wire must be copper with 75 °C (167 °F) minimum rating.
Figure 7-7: Safe Torque-off (STO) Terminal Plug
NOTICE The National Electrical Code and local electrical codes take
precedence over the values and methods provided.
IMPORTANT Stranded wires must terminate with ferrules to prevent short
circuits, per table D7 of ISO 13849.
Table 7-5: Safe Torque-off (STO) Connector Plug Wiring
Safe Torque-off (STO)
Connector Pin
Signal
Recommended
Wire Size
mm
2
(AWG)
Strip
Length
mm (in.)
Torque
Val ue
N•m (lb•in)
1SB+
0.14…1.5
(26…16)
10 (0.39) —
*